Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2020-12-01 → 2020-12-31 |
| TT | Health-based | Resolved | 2020-12-01 → 2020-12-31 |
| TT | Health-based | Resolved | 2020-12-01 → 2020-12-31 |
| TT | Health-based | Resolved | 2020-12-01 → 2020-12-31 |
| TT | Health-based | Resolved | 2020-12-01 → 2020-12-31 |
| TT | Health-based | Resolved | 2020-12-01 → 2020-12-31 |
| MCL | Health-based | Resolved | 2004-05-01 → 2004-05-31 |
| MCL | Health-based | Resolved | 2004-05-01 → 2004-05-31 |
| MCL | Health-based | Resolved | 2004-05-01 → 2004-05-31 |
| MCL | Health-based | Resolved | 2004-05-01 → 2004-05-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Chloroform | 36.77 µg/L No EPA limit set
worst single sample: 55 µg/L | 143/143 | SYR4 | 2012–2019 |
| Bromodichloromethane | 5.18 µg/L No EPA limit set
worst single sample: 6.96 µg/L | 141/142 | SYR4 | 2012–2019 |
| TTHM | 41.76 µg/L 52% of the EPA limit 80 µg/L
worst single sample: 62 µg/L | 125/125 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 41.38 µg/L 69% of the EPA limit 60 µg/L
worst single sample: 65.9 µg/L | 123/125 | SYR4 | 2012–2019 |
| Copper | 380.6 µg/L 29% of the EPA limit 1300 µg/L
worst single sample: 523 µg/L | 113/113 | SYR4 | 2013–2019 |
| Lead | 13.54 µg/L 90% of the EPA limit 15 µg/L
worst single sample: 40.5 µg/L | 77/118 | SYR4 | 2013–2019 |
| Dichloroacetic Acid | 14 µg/L No EPA limit set
worst single sample: 44 µg/L | 31/31 | SYR4 | 2017–2019 |
| Trichloroacetic Acid | 13 µg/L No EPA limit set
worst single sample: 22 µg/L | 31/31 | SYR4 | 2017–2019 |
| Dibromochloromethane | 1.509 µg/L No EPA limit set
worst single sample: 1.75 µg/L | 23/125 | SYR4 | 2012–2019 |
| Barium | 18.495 µg/L 0.9% of the EPA limit 2000 µg/L
worst single sample: 20.3 µg/L | 20/27 | SYR4 | 2012–2019 |
| Lead | 0.0011 mg/L 7.3% of the EPA limit 0.0150 mg/L | 15/15 | LCR | 2025 |
| Arsenic | 1.525 µg/L 15% of the EPA limit 10 µg/L
worst single sample: 1.6 µg/L | 6/32 | SYR4 | 2012–2019 |
| Mercury | 0.7530 µg/L 38% of the EPA limit 2 µg/L
worst single sample: 0.9300 µg/L | 5/27 | SYR4 | 2012–2019 |
| Selenium | 0.3950 µg/L 0.8% of the EPA limit 50 µg/L
worst single sample: 0.4100 µg/L | 4/27 | SYR4 | 2012–2019 |
| Beryllium, Total | 0.0748 µg/L 1.9% of the EPA limit 4 µg/L
worst single sample: 0.0760 µg/L | 2/27 | SYR4 | 2012–2019 |
| Cadmium | 0.0697 µg/L 1.4% of the EPA limit 5 µg/L
worst single sample: 0.0700 µg/L | 2/27 | SYR4 | 2012–2019 |
| Combined Uranium | 0.1409 µg/L 0.5% of the EPA limit 30 µg/L
worst single sample: 0.1430 µg/L | 2/2 | SYR4 | 2012 |
| Nitrate | 98 µg/L 1% of the EPA limit 10000 µg/L | 2/62 | SYR4 | 2012–2019 |
92 contaminants tested, none detected
Utility contact
Frequently asked questions about Schuylkill Co Mun Auth
Is Schuylkill Co Mun Auth tap water safe to drink?
EPA monitoring detected 18 contaminants in Schuylkill Co Mun Auth's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Schuylkill Co Mun Auth's water?
EPA monitoring detected Chloroform, Bromodichloromethane, TTHM, Total Haloacetic Acids (HAA5), Copper, and others. The full list with the level and data source for each is above.
How many people does Schuylkill Co Mun Auth serve?
Schuylkill Co Mun Auth reports serving 31,850 people in Pennsylvania, per its EPA record.
Has Schuylkill Co Mun Auth had any water quality violations?
The EPA has 227 violations on file for Schuylkill Co Mun Auth, of which 22 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.