Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2014-10-01 → 2014-10-31 |
| MCL | Health-based | Resolved | 2014-10-01 → 2014-10-31 |
| MCL | Health-based | Resolved | 2014-10-01 → 2014-10-31 |
| MCL | Health-based | Resolved | 2014-10-01 → 2014-10-31 |
| TT | Health-based | Resolved | 2009-01-01 → 2009-01-31 |
| TT | Health-based | Resolved | 2009-01-01 → 2009-01-31 |
| TT | Health-based | Resolved | 2009-01-01 → 2009-01-31 |
| TT | Health-based | Resolved | 2009-01-01 → 2009-01-31 |
| TT | Health-based | Resolved | 2009-01-01 → 2009-01-31 |
| TT | Health-based | Resolved | 2004-09-01 → 2004-09-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Chloroform | 82.435 µg/L No EPA limit set
worst single sample: 108 µg/L | 238/238 | SYR4 | 2012–2019 |
| TTHM | 90.715 µg/L 113% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 121 µg/L | 238/238 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 35.36 µg/L 59% of the EPA limit 60 µg/L
worst single sample: 48.6 µg/L | 238/238 | SYR4 | 2012–2019 |
| Bromodichloromethane | 9.4 µg/L No EPA limit set
worst single sample: 11.5 µg/L | 237/238 | SYR4 | 2012–2019 |
| Copper | 508.85 µg/L 39% of the EPA limit 1300 µg/L
worst single sample: 562 µg/L | 98/98 | SYR4 | 2013–2019 |
| Dibromochloromethane | 1.5 µg/L No EPA limit set
worst single sample: 1.6 µg/L | 88/238 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 19.195 µg/L No EPA limit set
worst single sample: 22.2 µg/L | 48/48 | SYR4 | 2018–2019 |
| Trichloroacetic Acid | 16.93 µg/L No EPA limit set
worst single sample: 18.5 µg/L | 48/48 | SYR4 | 2018–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 14/14 | LCR | 2025 |
| Lead | 4.45 µg/L 30% of the EPA limit 15 µg/L
worst single sample: 5 µg/L | 12/98 | SYR4 | 2013–2019 |
| Fluoride | 866.5 µg/L 22% of the EPA limit 4000 µg/L
worst single sample: 940 µg/L | 8/8 | SYR4 | 2012–2019 |
| Barium | 25.8 µg/L 1.3% of the EPA limit 2000 µg/L
worst single sample: 27 µg/L | 7/8 | SYR4 | 2012–2019 |
| Nitrate | 520 µg/L 5.2% of the EPA limit 10000 µg/L | 2/18 | SYR4 | 2012–2019 |
| Cyanide | 7 µg/L 3.5% of the EPA limit 200 µg/L | 1/8 | SYR4 | 2012–2019 |
96 contaminants tested, none detected
Utility contact
Frequently asked questions about Easton Area Water
Is Easton Area Water tap water safe to drink?
EPA monitoring detected 14 contaminants in Easton Area Water's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Easton Area Water's water?
EPA monitoring detected Chloroform, TTHM, Total Haloacetic Acids (HAA5), Bromodichloromethane, Copper, and others. The full list with the level and data source for each is above.
How many people does Easton Area Water serve?
Easton Area Water reports serving 96,867 people in Pennsylvania, per its EPA record.
Has Easton Area Water had any water quality violations?
The EPA has 210 violations on file for Easton Area Water, of which 26 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.