← Pennsylvania

Tap water quality report

Beaver Run Water Association

EPA monitoring tested this supplier for 79 contaminants and detected 15. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

79
contaminants tested
15
detected
50
people served
4
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Carbon

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

4
health-based violations
1,942
violations on file
61
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2012-04-01 → 2012-06-30
MCL Health-based Resolved 2012-04-01 → 2012-06-30
MCL Health-based Resolved 2012-04-01 → 2012-06-30
MCL Health-based Resolved 2012-04-01 → 2012-06-30
MR Monitoring Archived 2026-01-01 → 2026-03-31
MR Monitoring Archived 2026-01-01 → 2026-03-31
MR Monitoring Archived 2026-01-01 → 2026-03-31
MR Monitoring Archived 2026-01-01 → 2026-03-31
MR Monitoring Archived 2026-01-01 → 2026-03-31
MR Monitoring Archived 2026-01-01 → 2026-03-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
1743.5 µg/L 134%
of the EPA limit, at the 95th percentile of samples — 1300 µg/L
worst single sample: 4700 µg/L
50/50 SYR4 2012–2019
Lead
39.42 µg/L 263%
of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 121 µg/L
22/50 SYR4 2012–2019
Nitrate
747 µg/L 7.5%
of the EPA limit 10000 µg/L
20/36 SYR4 2012–2019
Lead
0.0258 mg/L 172%
above the EPA limit of 0.0150 mg/L
12/12 LCR 2025
Barium
54.8 µg/L 2.7%
of the EPA limit 2000 µg/L
worst single sample: 69.4 µg/L
6/6 SYR4 2012–2018
Antimony, Total
30.01 µg/L 500%
of the EPA limit, at the 95th percentile of samples — 6 µg/L
worst single sample: 33.2 µg/L
3/12 SYR4 2012–2018
Di(2-ethylhexyl) Phthalate
17.65 µg/L 294%
of the EPA limit, at the 95th percentile of samples — 6 µg/L
worst single sample: 18.5 µg/L
3/30 SYR4 2013–2019
Arsenic
2 µg/L 20%
of the EPA limit 10 µg/L
1/6 SYR4 2012–2018
Bromodichloromethane
0.6600 µg/L
No EPA limit set
1/1 SYR4 2019
Cadmium
3.9 µg/L 78%
of the EPA limit 5 µg/L
1/6 SYR4 2012–2018
Chloroform
0.5400 µg/L
No EPA limit set
1/1 SYR4 2019
Dibromochloromethane
0.8100 µg/L
No EPA limit set
1/1 SYR4 2019
Nitrite
3 µg/L 0.3%
of the EPA limit 1000 µg/L
1/18 SYR4 2012–2019
TTHM
2.01 µg/L 2.5%
of the EPA limit 80 µg/L
1/6 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
2.69 µg/L 4.5%
of the EPA limit 60 µg/L
1/6 SYR4 2012–2019
64 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,3,7,8-TCDD2,4,5-TP2,4-DAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalBromoformChlorobenzeneCyanideCarbofuranCarbon TetrachlorideChlordaneChromiumCombined UraniumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDibromoacetic AcidDichloroacetic AcidDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneFluorideGlyphosateHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidMonochloroacetic AcidOxamylPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroacetic AcidTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
JOHN VENTRE
Phone
610-844-3444

Frequently asked questions about Beaver Run Water Association

Is Beaver Run Water Association tap water safe to drink?

EPA monitoring detected 15 contaminants in Beaver Run Water Association's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Beaver Run Water Association's water?

EPA monitoring detected Copper, Lead, Nitrate, Lead, Barium, and others. The full list with the level and data source for each is above.

How many people does Beaver Run Water Association serve?

Beaver Run Water Association reports serving 50 people in Pennsylvania, per its EPA record.

Has Beaver Run Water Association had any water quality violations?

The EPA has 1942 violations on file for Beaver Run Water Association, of which 4 are health-based (a contaminant limit or required treatment was breached) and 61 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.