← Pennsylvania

Tap water quality report

Paw Winola

EPA monitoring tested this supplier for 80 contaminants and detected 13. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

80
contaminants tested
13
detected
63
people served
14
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Wyoming

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

14
health-based violations
1,516
violations on file
12
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 2018-04-24
TT Health-based Resolved 2018-04-24
TT Health-based Resolved 2018-04-24
TT Health-based Resolved 2018-04-24
TT Health-based Resolved 2017-05-08
TT Health-based Resolved 2017-05-08
TT Health-based Resolved 2017-05-08
TT Health-based Resolved 2017-05-08
TT Health-based Resolved 2017-05-08
TT Health-based Resolved 2017-05-08

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate
1150 µg/L 12%
of the EPA limit 10000 µg/L
16/18 SYR4 2012–2019
Copper
1006 µg/L 77%
of the EPA limit 1300 µg/L
worst single sample: 1270 µg/L
9/10 SYR4 2013–2018
Lead
0.0977 mg/L 651%
above the EPA limit of 0.0150 mg/L
5/5 LCR 2018
Combined Uranium
3.48436 µg/L 12%
of the EPA limit 30 µg/L
worst single sample: 3.6207 µg/L
4/4 SYR4 2013–2019
Lead
134.31 µg/L 895%
of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 150 µg/L
4/10 SYR4 2013–2018
Barium
220.8 µg/L 11%
of the EPA limit 2000 µg/L
worst single sample: 222 µg/L
3/4 SYR4 2012–2019
Bromodichloromethane
1.075 µg/L
No EPA limit set
worst single sample: 1.1 µg/L
2/2 SYR4 2013–2019
Cadmium
10.105 µg/L 202%
of the EPA limit, at the 95th percentile of samples — 5 µg/L
worst single sample: 10.5 µg/L
2/6 SYR4 2012–2019
Chloroform
1.8 µg/L
No EPA limit set
2/2 SYR4 2013–2019
TTHM
3.545 µg/L 4.4%
of the EPA limit 80 µg/L
worst single sample: 3.6 µg/L
2/3 SYR4 2013–2019
Dibromochloromethane
0.7000 µg/L
No EPA limit set
1/2 SYR4 2013–2019
Toluene
0.8000 µg/L 0.1%
of the EPA limit 1000 µg/L
1/4 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
2.81 µg/L 4.7%
of the EPA limit 60 µg/L
1/3 SYR4 2013–2019
67 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,3,7,8-TCDD2,4,5-TP2,4-DAntimony, TotalArsenicAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalBromoformChlorobenzeneCyanideCarbofuranCarbon TetrachlorideChlordaneChromiumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDibromoacetic AcidDichloroacetic AcidDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneFluorideGlyphosateGross Beta Particle ActivityHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidMonochloroacetic AcidNitriteOxamylPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroacetic AcidTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
DON KESSLER
Phone
610-248-7934

Frequently asked questions about Paw Winola

Is Paw Winola tap water safe to drink?

EPA monitoring detected 13 contaminants in Paw Winola's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Paw Winola's water?

EPA monitoring detected Nitrate, Copper, Lead, Combined Uranium, Lead, and others. The full list with the level and data source for each is above.

How many people does Paw Winola serve?

Paw Winola reports serving 63 people in Pennsylvania, per its EPA record.

Has Paw Winola had any water quality violations?

The EPA has 1516 violations on file for Paw Winola, of which 14 are health-based (a contaminant limit or required treatment was breached) and 12 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.