← Pennsylvania

Tap water quality report

Phoenixville Water Dept

EPA monitoring tested this supplier for 109 contaminants and detected 26. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

109
contaminants tested
26
detected
16,599
people served
53
health-based violations
Water source
Surface water
Ownership
Local government
Counties served
Chester

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

53
health-based violations
494
violations on file
0
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 2024-10-01 → 2024-12-31
TT Health-based Resolved 2024-10-01 → 2024-12-31
TT Health-based Resolved 2024-10-01 → 2024-12-31
TT Health-based Resolved 2024-10-01 → 2024-12-31
MCL Health-based Resolved 2014-08-01 → 2014-08-31
MCL Health-based Resolved 2014-08-01 → 2014-08-31
MCL Health-based Resolved 2014-08-01 → 2014-08-31
TT Health-based Resolved 2003-12-01 → 2003-12-31
TT Health-based Resolved 2003-12-01 → 2003-12-31
TT Health-based Resolved 2003-11-01 → 2003-11-30

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
Pfhxa 0.0090 µg/L 4/4 2024
Pfba 0.0573 µg/L 3/4 2024
PFBS 0.0098 µg/L 3/4 2024
PFOA 0.0059 µg/L 3/4 2024
Pfpea 0.0102 µg/L 3/4 2024
PFOS 0.0051 µg/L 2/4 2024
Pfhpa 0.0031 µg/L 1/4 2024

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
TTHM
98.195 µg/L 123%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 126 µg/L
128/128 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
60.47 µg/L 101%
of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 144.3 µg/L
127/128 SYR4 2012–2019
Chloroform
77.8 µg/L
No EPA limit set
worst single sample: 95 µg/L
92/92 SYR4 2017–2019
Copper
535 µg/L 41%
of the EPA limit 1300 µg/L
worst single sample: 1100 µg/L
76/90 SYR4 2013–2019
Bromodichloromethane
30.01 µg/L
No EPA limit set
worst single sample: 33.7 µg/L
48/48 SYR4 2017–2019
Dichloroacetic Acid
40.605 µg/L
No EPA limit set
worst single sample: 70.4 µg/L
48/48 SYR4 2017–2019
Trichloroacetic Acid
44.41 µg/L
No EPA limit set
worst single sample: 68.8 µg/L
48/48 SYR4 2017–2019
Dibromochloromethane
12.16 µg/L
No EPA limit set
worst single sample: 15.8 µg/L
47/48 SYR4 2017–2019
Bromoform
1.6 µg/L
No EPA limit set
worst single sample: 2.1 µg/L
31/48 SYR4 2017–2019
Dibromoacetic Acid
2.39 µg/L
No EPA limit set
worst single sample: 2.9 µg/L
18/48 SYR4 2017–2019
Lead
10.24 µg/L 68%
of the EPA limit 15 µg/L
worst single sample: 30 µg/L
17/90 SYR4 2013–2019
Nitrate
3600 µg/L 36%
of the EPA limit 10000 µg/L
16/16 SYR4 2012–2019
Lead
0.0010 mg/L 6.7%
of the EPA limit 0.0150 mg/L
14/14 LCR 2025
Barium
44.2 µg/L 2.2%
of the EPA limit 2000 µg/L
worst single sample: 46 µg/L
7/7 SYR4 2012–2018
Chromium
2.67 µg/L 2.7%
of the EPA limit 100 µg/L
worst single sample: 2.7 µg/L
7/7 SYR4 2012–2018
Fluoride
573 µg/L 14%
of the EPA limit 4000 µg/L
worst single sample: 600 µg/L
7/7 SYR4 2012–2018
Monochloroacetic Acid
4.835 µg/L
No EPA limit set
worst single sample: 5.1 µg/L
6/48 SYR4 2017–2019
Selenium
2.49 µg/L 5%
of the EPA limit 50 µg/L
worst single sample: 2.5 µg/L
3/7 SYR4 2012–2018
Monobromoacetic Acid
1.53 µg/L
No EPA limit set
1/48 SYR4 2017–2019
83 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,3,7,8-TCDD2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalArsenicAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateGross Beta Particle ActivityHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNetfosaaNfdhaNmefosaaNitriteOxamylPfdaPfdoaPfeesaPfhpsPFHXSPfmbaPfmpaPFNAPfpesPftaPftrdaPfunaPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
BRIAN WATSON
Phone
610-933-8801

Frequently asked questions about Phoenixville Water Dept

Is Phoenixville Water Dept tap water safe to drink?

EPA monitoring detected 26 contaminants in Phoenixville Water Dept's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Phoenixville Water Dept's water?

EPA monitoring detected TTHM, Total Haloacetic Acids (HAA5), Chloroform, Copper, Bromodichloromethane, and others. The full list with the level and data source for each is above.

How many people does Phoenixville Water Dept serve?

Phoenixville Water Dept reports serving 16,599 people in Pennsylvania, per its EPA record.

Has Phoenixville Water Dept had any water quality violations?

The EPA has 494 violations on file for Phoenixville Water Dept, of which 53 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.