← Pennsylvania

Tap water quality report

Plumstead Twp Summer Hill Mead

EPA monitoring tested this supplier for 79 contaminants and detected 19. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

79
contaminants tested
19
detected
1,284
people served
12
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Bucks

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

12
health-based violations
280
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2018-04-01 → 2018-06-30
MCL Health-based Resolved 2018-04-01 → 2018-06-30
MCL Health-based Resolved 2018-04-01 → 2018-06-30
MCL Health-based Resolved 2018-04-01 → 2018-06-30
MCL Health-based Resolved 2018-01-01 → 2018-03-31
MCL Health-based Resolved 2018-01-01 → 2018-03-31
MCL Health-based Resolved 2018-01-01 → 2018-03-31
MCL Health-based Resolved 2018-01-01 → 2018-03-31
MCL Health-based Resolved 2017-10-01 → 2017-12-31
MCL Health-based Resolved 2017-10-01 → 2017-12-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
455.4 µg/L 35%
of the EPA limit 1300 µg/L
worst single sample: 540 µg/L
65/65 SYR4 2013–2019
Lead
1 µg/L 6.7%
of the EPA limit 15 µg/L
12/65 SYR4 2013–2019
Nitrate
1000 µg/L 10%
of the EPA limit 10000 µg/L
12/32 SYR4 2012–2019
Bromodichloromethane
14.48 µg/L
No EPA limit set
worst single sample: 15.2 µg/L
10/10 SYR4 2014–2019
Chloroform
19.785 µg/L
No EPA limit set
worst single sample: 21 µg/L
10/10 SYR4 2014–2019
Dibromochloromethane
8.98 µg/L
No EPA limit set
worst single sample: 9.9 µg/L
9/10 SYR4 2014–2019
TTHM
44.16 µg/L 55%
of the EPA limit 80 µg/L
worst single sample: 45.7 µg/L
8/8 SYR4 2014–2019
Total Haloacetic Acids (HAA5)
10.24 µg/L 17%
of the EPA limit 60 µg/L
worst single sample: 10.3 µg/L
7/8 SYR4 2014–2019
Bromoform
2.4 µg/L
No EPA limit set
worst single sample: 2.6 µg/L
6/8 SYR4 2014–2019
Combined Uranium
10.7328 µg/L 36%
of the EPA limit 30 µg/L
worst single sample: 11.2808 µg/L
6/10 SYR4 2012–2019
Arsenic
2.985 µg/L 30%
of the EPA limit 10 µg/L
worst single sample: 3 µg/L
4/6 SYR4 2012–2018
Barium
96.055 µg/L 4.8%
of the EPA limit 2000 µg/L
worst single sample: 96.1 µg/L
4/6 SYR4 2012–2018
Antimony, Total
0.2355 µg/L 3.9%
of the EPA limit 6 µg/L
worst single sample: 0.2400 µg/L
2/6 SYR4 2012–2018
Chromium
1.656 µg/L 1.7%
of the EPA limit 100 µg/L
worst single sample: 1.7 µg/L
2/6 SYR4 2012–2018
Dibromoacetic Acid
2 µg/L
No EPA limit set
2/2 SYR4 2018–2019
Dichloroacetic Acid
6 µg/L
No EPA limit set
2/2 SYR4 2018–2019
Selenium
0.9895 µg/L 2%
of the EPA limit 50 µg/L
worst single sample: 0.9900 µg/L
2/6 SYR4 2012–2018
Trichloroacetic Acid
2 µg/L
No EPA limit set
2/2 SYR4 2018–2019
Cadmium
0.0900 µg/L 1.8%
of the EPA limit 5 µg/L
1/6 SYR4 2012–2018
60 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,3,7,8-TCDD2,4,5-TP2,4-DAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCarbofuranCarbon TetrachlorideChlordaneDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneFluorideGlyphosateGross Beta Particle ActivityHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidMonochloroacetic AcidNitriteOxamylPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
Stacey Mulhollan
Phone
215-766-8914

Frequently asked questions about Plumstead Twp Summer Hill Mead

Is Plumstead Twp Summer Hill Mead tap water safe to drink?

EPA monitoring detected 19 contaminants in Plumstead Twp Summer Hill Mead's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Plumstead Twp Summer Hill Mead's water?

EPA monitoring detected Copper, Lead, Nitrate, Bromodichloromethane, Chloroform, and others. The full list with the level and data source for each is above.

How many people does Plumstead Twp Summer Hill Mead serve?

Plumstead Twp Summer Hill Mead reports serving 1,284 people in Pennsylvania, per its EPA record.

Has Plumstead Twp Summer Hill Mead had any water quality violations?

The EPA has 280 violations on file for Plumstead Twp Summer Hill Mead, of which 12 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.