Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2018-12-01 → 2018-12-31 |
| TT | Health-based | Resolved | 2018-12-01 → 2018-12-31 |
| TT | Health-based | Resolved | 2018-12-01 → 2018-12-31 |
| TT | Health-based | Resolved | 2018-12-01 → 2018-12-31 |
| TT | Health-based | Resolved | 2016-08-01 → 2016-08-31 |
| TT | Health-based | Resolved | 2016-08-01 → 2016-08-31 |
| TT | Health-based | Resolved | 2016-08-01 → 2016-08-31 |
| TT | Health-based | Resolved | 2016-08-01 → 2016-08-31 |
| TT | Health-based | Resolved | 2016-07-01 → 2016-07-31 |
| TT | Health-based | Resolved | 2016-07-01 → 2016-07-31 |
PFAS detected
| Contaminant | Max | Detection rate | Period |
|---|---|---|---|
| Pfba | 0.0070 µg/L | 2/40 | 2025 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 507.4 µg/L 39% of the EPA limit 1300 µg/L
worst single sample: 1440 µg/L | 249/249 | SYR4 | 2013–2019 |
| Dibromochloromethane | 6.404 µg/L No EPA limit set
worst single sample: 12.2 µg/L | 125/126 | SYR4 | 2012–2019 |
| Bromodichloromethane | 12.29 µg/L No EPA limit set
worst single sample: 17.1 µg/L | 112/113 | SYR4 | 2012–2019 |
| Chloroform | 39.69 µg/L No EPA limit set
worst single sample: 58.2 µg/L | 107/111 | SYR4 | 2012–2019 |
| TTHM | 53.64 µg/L 67% of the EPA limit 80 µg/L
worst single sample: 74.4 µg/L | 105/105 | SYR4 | 2012–2019 |
| Lead | 6 µg/L 40% of the EPA limit 15 µg/L
worst single sample: 19.7 µg/L | 103/251 | SYR4 | 2013–2019 |
| Total Haloacetic Acids (HAA5) | 18.7 µg/L 31% of the EPA limit 60 µg/L
worst single sample: 26.2 µg/L | 92/105 | SYR4 | 2012–2019 |
| Nitrate | 3100 µg/L 31% of the EPA limit 10000 µg/L
worst single sample: 8100 µg/L | 90/100 | SYR4 | 2012–2019 |
| Bromoform | 3.0515 µg/L No EPA limit set
worst single sample: 4.48 µg/L | 52/122 | SYR4 | 2012–2019 |
| Combined Uranium | 46.8818 µg/L 156% of the EPA limit, at the 95th percentile of samples — 30 µg/L
worst single sample: 51.849 µg/L | 24/24 | SYR4 | 2014–2017 |
| Dichloroacetic Acid | 14.49 µg/L No EPA limit set
worst single sample: 16.2 µg/L | 23/23 | SYR4 | 2018–2019 |
| Trichloroacetic Acid | 9.711 µg/L No EPA limit set
worst single sample: 10.6 µg/L | 23/23 | SYR4 | 2018–2019 |
| Arsenic | 8.8 µg/L 88% of the EPA limit 10 µg/L
worst single sample: 36.4 µg/L | 21/21 | SYR4 | 2012–2018 |
| Lead | 0.00060 mg/L 4% of the EPA limit 0.0150 mg/L | 14/14 | LCR | 2025 |
| Barium | 415 µg/L 21% of the EPA limit 2000 µg/L
worst single sample: 481 µg/L | 13/13 | SYR4 | 2012–2015 |
| Di(2-ethylhexyl) Phthalate | 3.2355 µg/L 54% of the EPA limit 6 µg/L
worst single sample: 5.32 µg/L | 12/53 | SYR4 | 2012–2019 |
| Chromium | 12.4 µg/L 12% of the EPA limit 100 µg/L
worst single sample: 19.1 µg/L | 11/11 | SYR4 | 2012–2015 |
| Selenium | 3.27 µg/L 6.5% of the EPA limit 50 µg/L
worst single sample: 3.3 µg/L | 7/8 | SYR4 | 2012–2015 |
| Mercury | 0.0257 µg/L 1.3% of the EPA limit 2 µg/L
worst single sample: 0.0280 µg/L | 6/8 | SYR4 | 2012–2015 |
| Lithium | 20.6 µg/L No EPA limit set | 6/40 | UCMR-5 | 2025 |
| Nitrite | 109.5 µg/L 11% of the EPA limit 1000 µg/L
worst single sample: 110 µg/L | 2/50 | SYR4 | 2012–2019 |
| Tetrachloroethylene | 0.8720 µg/L 17% of the EPA limit 5 µg/L
worst single sample: 0.9000 µg/L | 2/52 | SYR4 | 2012–2019 |
| 1,1-Dichloroethylene | 0.3200 µg/L 4.6% of the EPA limit 7 µg/L | 1/52 | SYR4 | 2012–2019 |
| Carbon Tetrachloride | 0.1100 µg/L 2.2% of the EPA limit 5 µg/L | 1/52 | SYR4 | 2012–2019 |
| Heptachlor | 0.1100 µg/L 27% of the EPA limit 0.4000 µg/L | 1/40 | SYR4 | 2012–2019 |
| cis-1,2-Dichloroethylene | 0.1300 µg/L 0.2% of the EPA limit 70 µg/L | 1/52 | SYR4 | 2012–2019 |
83 contaminants tested, none detected
Utility contact
Frequently asked questions about Nwwa Warrington Township
Is Nwwa Warrington Township tap water safe to drink?
EPA monitoring detected 27 contaminants in Nwwa Warrington Township's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Nwwa Warrington Township's water?
EPA monitoring detected Copper, Dibromochloromethane, Bromodichloromethane, Chloroform, TTHM, and others. The full list with the level and data source for each is above.
How many people does Nwwa Warrington Township serve?
Nwwa Warrington Township reports serving 21,588 people in Pennsylvania, per its EPA record.
Has Nwwa Warrington Township had any water quality violations?
The EPA has 1671 violations on file for Nwwa Warrington Township, of which 26 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.