Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 1993-06-01 → 1993-06-30 |
| MCL | Health-based | Resolved | 1993-03-01 → 1993-03-31 |
| MCL | Health-based | Resolved | 1991-12-01 → 1991-12-31 |
| MCL | Health-based | Archived | 1991-12-01 → 1991-12-31 |
| MCL | Health-based | Resolved | 1991-11-01 → 1991-11-30 |
| MCL | Health-based | Archived | 1991-11-01 → 1991-11-30 |
| MR | Monitoring | Resolved | 2025-07-01 → 2025-09-30 |
| MR | Monitoring | Resolved | 2025-07-01 → 2025-09-30 |
| MR | Monitoring | Archived | 2024-12-01 → 2024-12-31 |
| MR | Monitoring | Archived | 2024-11-01 → 2024-11-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Lead | 0.0070 mg/L 47% of the EPA limit 0.0150 mg/L | 17/17 | LCR | 2025 |
| Nitrate | 6370 µg/L 64% of the EPA limit 10000 µg/L | 16/32 | SYR4 | 2012–2019 |
| Copper | 98.6 µg/L 7.6% of the EPA limit 1300 µg/L
worst single sample: 107 µg/L | 4/15 | SYR4 | 2013–2019 |
| Combined Uranium | 2.988 µg/L 10% of the EPA limit 30 µg/L
worst single sample: 3 µg/L | 4/6 | SYR4 | 2014–2017 |
| Gross Alpha, Excl. Radon And U | 9.6625 pCi/L 64% of the EPA limit 15 pCi/L
worst single sample: 10.9 pCi/L | 4/6 | SYR4 | 2014–2017 |
| Lead | 2.95 µg/L 20% of the EPA limit 15 µg/L
worst single sample: 3 µg/L | 3/15 | SYR4 | 2013–2019 |
| Barium | 21.245 µg/L 1.1% of the EPA limit 2000 µg/L
worst single sample: 21.5 µg/L | 2/2 | SYR4 | 2017–2018 |
| Chromium | 3.171 µg/L 3.2% of the EPA limit 100 µg/L
worst single sample: 3.27 µg/L | 2/2 | SYR4 | 2017–2018 |
| Fluoride | 651.4 µg/L 16% of the EPA limit 4000 µg/L
worst single sample: 666 µg/L | 2/2 | SYR4 | 2017–2018 |
| Nitrate-Nitrite | 6066.55 µg/L 61% of the EPA limit 10000 µg/L
worst single sample: 6380 µg/L | 2/2 | SYR4 | 2017–2018 |
| TTHM | 27.49 µg/L 34% of the EPA limit 80 µg/L
worst single sample: 27.9 µg/L | 2/2 | SYR4 | 2014–2017 |
| Total Haloacetic Acids (HAA5) | 1.786 µg/L 3% of the EPA limit 60 µg/L
worst single sample: 1.8 µg/L | 2/2 | SYR4 | 2014–2017 |
| Arsenic | 1.51 µg/L 15% of the EPA limit 10 µg/L | 1/2 | SYR4 | 2017–2018 |
| Nitrite | 167 µg/L 17% of the EPA limit 1000 µg/L | 1/2 | SYR4 | 2017–2018 |
58 contaminants tested, none detected
Utility contact
Frequently asked questions about Rufus Public Works
Is Rufus Public Works tap water safe to drink?
EPA monitoring detected 14 contaminants in Rufus Public Works's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Rufus Public Works's water?
EPA monitoring detected Lead, Nitrate, Copper, Combined Uranium, Gross Alpha, Excl. Radon And U, and others. The full list with the level and data source for each is above.
How many people does Rufus Public Works serve?
Rufus Public Works reports serving 270 people in Oregon, per its EPA record.
Has Rufus Public Works had any water quality violations?
The EPA has 25 violations on file for Rufus Public Works, of which 6 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.