← Oklahoma

Tap water quality report

Phillips Rwd #1

EPA monitoring tested this supplier for 14 contaminants and detected 14. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

14
contaminants tested
14
detected
140
people served
17
health-based violations
Water source
SWP
Ownership
Local government
Counties served
Coal

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

17
health-based violations
129
violations on file
4
still open
ViolationTypeStatusPeriod
TT Health-based Addressed 2024-10-17
TT Health-based Addressed 2024-10-17
MCL Health-based Resolved 2019-04-01 → 2019-06-30
MCL Health-based Resolved 2019-04-01 → 2019-06-30
MCL Health-based Resolved 2019-04-01 → 2019-06-30
MCL Health-based Resolved 2019-04-01 → 2019-06-30
MCL Health-based Resolved 2016-01-01 → 2016-03-31
MCL Health-based Resolved 2016-01-01 → 2016-03-31
MCL Health-based Resolved 2016-01-01 → 2016-03-31
MCL Health-based Resolved 2016-01-01 → 2016-03-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
523.2 µg/L 40%
of the EPA limit 1300 µg/L
worst single sample: 2490 µg/L
33/45 SYR4 2013–2019
Chloroform
84.8 µg/L
No EPA limit set
worst single sample: 98.5 µg/L
21/22 SYR4 2014–2019
TTHM
114 µg/L 143%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 126 µg/L
21/22 SYR4 2014–2019
Bromodichloromethane
21.63 µg/L
No EPA limit set
worst single sample: 22.2 µg/L
20/22 SYR4 2014–2019
Dibromochloromethane
10.3 µg/L
No EPA limit set
worst single sample: 12.1 µg/L
19/22 SYR4 2014–2019
Bromoform
4.66 µg/L
No EPA limit set
worst single sample: 6.79 µg/L
16/22 SYR4 2014–2019
Lead
0.00046 mg/L 3.1%
of the EPA limit 0.0150 mg/L
16/16 LCR 2025
Total Haloacetic Acids (HAA5)
54.45 µg/L 91%
of the EPA limit 60 µg/L
worst single sample: 58.2 µg/L
16/22 SYR4 2014–2019
Trichloroacetic Acid
29.66 µg/L
No EPA limit set
worst single sample: 33.3 µg/L
15/22 SYR4 2014–2019
Dichloroacetic Acid
24.34 µg/L
No EPA limit set
worst single sample: 28 µg/L
13/22 SYR4 2014–2019
Lead
188.787 µg/L 1259%
of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 290 µg/L
8/45 SYR4 2013–2019
Monochloroacetic Acid
4.2185 µg/L
No EPA limit set
worst single sample: 4.4 µg/L
4/22 SYR4 2014–2019
Dibromoacetic Acid
3.035 µg/L
No EPA limit set
worst single sample: 3.1 µg/L
2/22 SYR4 2014–2019
Monobromoacetic Acid
1.24 µg/L
No EPA limit set
1/22 SYR4 2014–2019

Utility contact

Contact
PHILLIPS RWD #1
Phone
580-258-0174
Email
[email protected]

Frequently asked questions about Phillips Rwd #1

Is Phillips Rwd #1 tap water safe to drink?

EPA monitoring detected 14 contaminants in Phillips Rwd #1's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Phillips Rwd #1's water?

EPA monitoring detected Copper, Chloroform, TTHM, Bromodichloromethane, Dibromochloromethane, and others. The full list with the level and data source for each is above.

How many people does Phillips Rwd #1 serve?

Phillips Rwd #1 reports serving 140 people in Oklahoma, per its EPA record.

Has Phillips Rwd #1 had any water quality violations?

The EPA has 129 violations on file for Phillips Rwd #1, of which 17 are health-based (a contaminant limit or required treatment was breached) and 4 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.