Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Addressed | 2024-10-17 |
| TT | Health-based | Addressed | 2024-10-17 |
| MCL | Health-based | Resolved | 2015-07-01 → 2015-07-31 |
| MCL | Health-based | Resolved | 2015-07-01 → 2015-07-31 |
| MCL | Health-based | Resolved | 2015-07-01 → 2015-07-31 |
| MCL | Health-based | Resolved | 2015-07-01 → 2015-07-31 |
| MCL | Health-based | Resolved | 2012-10-01 → 2012-12-31 |
| MCL | Health-based | Resolved | 2012-10-01 → 2012-12-31 |
| MCL | Health-based | Resolved | 2012-10-01 → 2012-12-31 |
| MCL | Health-based | Resolved | 2012-10-01 → 2012-12-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 219.2 µg/L 17% of the EPA limit 1300 µg/L
worst single sample: 312 µg/L | 79/80 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 1500 µg/L 15% of the EPA limit 10000 µg/L
worst single sample: 6130 µg/L | 42/42 | SYR4 | 2012–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 20/20 | LCR | 2025 |
| TTHM | 184.23 µg/L 230% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 248.4 µg/L | 19/26 | SYR4 | 2012–2019 |
| Bromodichloromethane | 64.745 µg/L No EPA limit set
worst single sample: 85.4 µg/L | 18/38 | SYR4 | 2012–2019 |
| Dibromochloromethane | 50.465 µg/L No EPA limit set
worst single sample: 68.4 µg/L | 18/38 | SYR4 | 2012–2019 |
| Bromoform | 11.34 µg/L No EPA limit set
worst single sample: 14.7 µg/L | 17/38 | SYR4 | 2012–2019 |
| Chloroform | 66.175 µg/L No EPA limit set
worst single sample: 79.9 µg/L | 16/38 | SYR4 | 2012–2019 |
| Combined Uranium | 7.98 µg/L 27% of the EPA limit 30 µg/L
worst single sample: 8.1 µg/L | 7/12 | SYR4 | 2017–2019 |
| Dibromoacetic Acid | 16.74 µg/L No EPA limit set
worst single sample: 19.2 µg/L | 7/20 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 36.23 µg/L No EPA limit set
worst single sample: 41 µg/L | 7/20 | SYR4 | 2012–2019 |
| Gross Alpha, Excl. Radon And U | 9.99 pCi/L 67% of the EPA limit 15 pCi/L
worst single sample: 10.5 pCi/L | 7/12 | SYR4 | 2017–2019 |
| Barium | 352.25 µg/L 18% of the EPA limit 2000 µg/L
worst single sample: 383 µg/L | 6/6 | SYR4 | 2017–2019 |
| Total Haloacetic Acids (HAA5) | 70.525 µg/L 118% of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 72 µg/L | 6/26 | SYR4 | 2012–2019 |
| Picloram | 0.7030 µg/L 0.1% of the EPA limit 500 µg/L
worst single sample: 0.7100 µg/L | 3/20 | SYR4 | 2018–2019 |
| Trichloroacetic Acid | 15.53 µg/L No EPA limit set
worst single sample: 15.7 µg/L | 3/20 | SYR4 | 2012–2019 |
| Lithium | 53 µg/L No EPA limit set | 3/8 | UCMR-5 | 2024 |
| Arsenic | 3.09 µg/L 31% of the EPA limit 10 µg/L
worst single sample: 3.1 µg/L | 2/10 | SYR4 | 2013–2019 |
| Fluoride | 403 µg/L 10% of the EPA limit 4000 µg/L
worst single sample: 410 µg/L | 2/4 | SYR4 | 2017–2019 |
| Lead | 10.441 µg/L 70% of the EPA limit 15 µg/L
worst single sample: 10.6 µg/L | 2/80 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 2.945 µg/L No EPA limit set
worst single sample: 3 µg/L | 2/20 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 4.14 µg/L No EPA limit set
worst single sample: 4.2 µg/L | 2/20 | SYR4 | 2012–2019 |
| 2,4-D | 0.3700 µg/L 0.5% of the EPA limit 70 µg/L | 1/20 | SYR4 | 2018–2019 |
| Diquat | 1.6 µg/L 8% of the EPA limit 20 µg/L | 1/19 | SYR4 | 2018–2019 |
| Pentachlorophenol | 0.2100 µg/L 21% of the EPA limit 1 µg/L | 1/20 | SYR4 | 2018–2019 |
65 contaminants tested, none detected
Utility contact
Frequently asked questions about Stephens Co Rwd #5
Is Stephens Co Rwd #5 tap water safe to drink?
EPA monitoring detected 25 contaminants in Stephens Co Rwd #5's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Stephens Co Rwd #5's water?
EPA monitoring detected Copper, Nitrate-Nitrite, Lead, TTHM, Bromodichloromethane, and others. The full list with the level and data source for each is above.
How many people does Stephens Co Rwd #5 serve?
Stephens Co Rwd #5 reports serving 6,426 people in Oklahoma, per its EPA record.
Has Stephens Co Rwd #5 had any water quality violations?
The EPA has 41 violations on file for Stephens Co Rwd #5, of which 22 are health-based (a contaminant limit or required treatment was breached) and 6 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.