Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2015-07-01 → 2015-09-30 |
| MCL | Health-based | Resolved | 2015-07-01 → 2015-09-30 |
| MCL | Health-based | Resolved | 2015-07-01 → 2015-09-30 |
| Other | Monitoring | Unaddressed | 2020-02-10 |
| MR | Monitoring | Resolved | 2010-10-01 |
| MR | Monitoring | Resolved | 2010-10-01 |
| MR | Monitoring | Resolved | 2010-10-01 |
| MR | Monitoring | Resolved | 2010-10-01 |
| MR | Monitoring | Resolved | 2010-04-01 → 2010-06-30 |
| MR | Monitoring | Resolved | 2010-04-01 → 2010-06-30 |
PFAS detected
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Bromodichloromethane | 14.878 µg/L No EPA limit set
worst single sample: 18.82 µg/L | 64/65 | SYR4 | 2012–2019 |
| Chloroform | 76.3575 µg/L No EPA limit set
worst single sample: 85.3 µg/L | 64/65 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 41.7055 µg/L No EPA limit set
worst single sample: 43.86 µg/L | 64/64 | SYR4 | 2012–2019 |
| TTHM | 90.3605 µg/L 113% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 107.1 µg/L | 64/65 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 49.522 µg/L 83% of the EPA limit 60 µg/L
worst single sample: 69.87 µg/L | 64/64 | SYR4 | 2012–2019 |
| Copper | 60.315 µg/L 4.6% of the EPA limit 1300 µg/L
worst single sample: 71.3 µg/L | 52/61 | SYR4 | 2014–2018 |
| Trichloroacetic Acid | 13.395 µg/L No EPA limit set
worst single sample: 22.21 µg/L | 51/64 | SYR4 | 2012–2019 |
| Dibromochloromethane | 3.955 µg/L No EPA limit set
worst single sample: 4.78 µg/L | 28/65 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 15.996 µg/L No EPA limit set
worst single sample: 20.1 µg/L | 28/64 | SYR4 | 2012–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 25/25 | LCR | 2025 |
| Monobromoacetic Acid | 2.464 µg/L No EPA limit set
worst single sample: 2.49 µg/L | 3/64 | SYR4 | 2012–2019 |
| Lead | 36.5 µg/L 243% of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 38 µg/L | 2/61 | SYR4 | 2014–2018 |
| Dibromoacetic Acid | 1.26 µg/L No EPA limit set | 1/64 | SYR4 | 2012–2019 |
27 contaminants tested, none detected
Utility contact
Frequently asked questions about Mcdonald Village
Is Mcdonald Village tap water safe to drink?
EPA monitoring detected 17 contaminants in Mcdonald Village's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Mcdonald Village's water?
EPA monitoring detected Bromodichloromethane, Chloroform, Dichloroacetic Acid, TTHM, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.
How many people does Mcdonald Village serve?
Mcdonald Village reports serving 4,236 people in Ohio, per its EPA record.
Has Mcdonald Village had any water quality violations?
The EPA has 22 violations on file for Mcdonald Village, of which 3 are health-based (a contaminant limit or required treatment was breached) and 1 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.