Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2024-10-17 |
| TT | Health-based | Resolved | 2024-10-17 |
| TT | Health-based | Resolved | 2024-10-17 |
| TT | Health-based | Resolved | 2024-10-17 |
| MCL | Health-based | Archived | 2015-07-01 → 2015-07-31 |
| MCL | Health-based | Archived | 2015-07-01 → 2015-07-31 |
| RPT | Monitoring | Resolved | 2024-10-17 |
| RPT | Monitoring | Resolved | 2024-10-17 |
| RPT | Monitoring | Resolved | 2024-10-17 |
| RPT | Monitoring | Resolved | 2024-10-17 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Bromodichloromethane | 18.765 µg/L No EPA limit set
worst single sample: 22.3 µg/L | 128/128 | SYR4 | 2012–2019 |
| Chloroform | 81.095 µg/L No EPA limit set
worst single sample: 122 µg/L | 128/128 | SYR4 | 2012–2019 |
| TTHM | 100.65 µg/L 126% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 149 µg/L | 128/128 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 61.86 µg/L 103% of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 99.2 µg/L | 128/128 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 32.65 µg/L No EPA limit set
worst single sample: 52 µg/L | 127/128 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 29.89 µg/L No EPA limit set
worst single sample: 54.8 µg/L | 127/128 | SYR4 | 2012–2019 |
| Dibromochloromethane | 4.78 µg/L No EPA limit set
worst single sample: 17.2 µg/L | 125/128 | SYR4 | 2012–2019 |
| Copper | 281.8 µg/L 22% of the EPA limit 1300 µg/L
worst single sample: 1410 µg/L | 69/90 | SYR4 | 2012–2018 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 19/19 | LCR | 2024 |
| Monochloroacetic Acid | 16.77 µg/L No EPA limit set
worst single sample: 18.3 µg/L | 19/128 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 1.25 µg/L No EPA limit set
worst single sample: 1.3 µg/L | 11/128 | SYR4 | 2012–2019 |
| Lead | 9.2705 µg/L 62% of the EPA limit 15 µg/L
worst single sample: 10.8 µg/L | 8/89 | SYR4 | 2012–2018 |
| Bromoform | 1.085 µg/L No EPA limit set
worst single sample: 1.1 µg/L | 4/128 | SYR4 | 2012–2019 |
31 contaminants tested, none detected
Utility contact
Frequently asked questions about Stow Public Water
Is Stow Public Water tap water safe to drink?
EPA monitoring detected 13 contaminants in Stow Public Water's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Stow Public Water's water?
EPA monitoring detected Bromodichloromethane, Chloroform, TTHM, Total Haloacetic Acids (HAA5), Dichloroacetic Acid, and others. The full list with the level and data source for each is above.
How many people does Stow Public Water serve?
Stow Public Water reports serving 35,437 people in Ohio, per its EPA record.
Has Stow Public Water had any water quality violations?
The EPA has 16 violations on file for Stow Public Water, of which 6 are health-based (a contaminant limit or required treatment was breached) and 2 remain open. The rest are monitoring or reporting failures.
Where does this data come from?