← Ohio

Tap water quality report

West Lake Village Mhp

EPA monitoring tested this supplier for 52 contaminants and detected 16. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

52
contaminants tested
16
detected
83
people served
20
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Shelby

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

20
health-based violations
87
violations on file
1
still open
ViolationTypeStatusPeriod
MCL Health-based Archived 2010-10-01 → 2010-12-31
MCL Health-based Archived 2010-10-01 → 2010-12-31
MCL Health-based Archived 2010-10-01 → 2010-12-31
MCL Health-based Archived 2010-10-01 → 2010-12-31
MCL Health-based Resolved 2009-04-01 → 2009-06-30
MCL Health-based Resolved 2009-04-01 → 2009-06-30
MCL Health-based Resolved 2009-04-01 → 2009-06-30
MCL Health-based Resolved 2009-04-01 → 2009-06-30
MCL Health-based Resolved 2009-04-01 → 2009-06-30
MCL Health-based Resolved 2009-01-01 → 2009-03-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
24/24 LCR 2025
Bromodichloromethane
6.334 µg/L
No EPA limit set
worst single sample: 6.63 µg/L
9/11 SYR4 2013–2019
Chloroform
7.108 µg/L
No EPA limit set
worst single sample: 7.28 µg/L
9/11 SYR4 2013–2019
Arsenic
8.6445 µg/L 86%
of the EPA limit 10 µg/L
worst single sample: 8.83 µg/L
8/34 SYR4 2012–2019
Dibromochloromethane
3.643 µg/L
No EPA limit set
worst single sample: 3.65 µg/L
8/11 SYR4 2013–2019
TTHM
16 µg/L 20%
of the EPA limit 80 µg/L
worst single sample: 16.39 µg/L
6/7 SYR4 2013–2019
Trichloroacetic Acid
3.206 µg/L
No EPA limit set
worst single sample: 3.46 µg/L
5/7 SYR4 2013–2019
Dichloroacetic Acid
2.618 µg/L
No EPA limit set
worst single sample: 2.66 µg/L
4/7 SYR4 2013–2019
Fluoride
2429 µg/L 61%
of the EPA limit 4000 µg/L
worst single sample: 2520 µg/L
3/3 SYR4 2013–2019
Nitrate
1840 µg/L 18%
of the EPA limit 10000 µg/L
2/16 SYR4 2012–2019
Copper
50 µg/L 3.8%
of the EPA limit 1300 µg/L
1/20 SYR4 2013–2019
Dibromoacetic Acid
1.24 µg/L
No EPA limit set
1/7 SYR4 2013–2019
Nitrate-Nitrite
1840 µg/L 18%
of the EPA limit 10000 µg/L
1/5 SYR4 2012–2016
Toluene
0.6000 µg/L 0.1%
of the EPA limit 1000 µg/L
1/4 SYR4 2013–2019
Total Haloacetic Acids (HAA5)
7.36 µg/L 12%
of the EPA limit 60 µg/L
1/7 SYR4 2013–2019
Xylenes, Total
0.9300 µg/L 0%
of the EPA limit 10000 µg/L
1/4 SYR4 2013–2019
36 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-DichloropropaneAntimony, TotalAtrazineBariumBenzeneBeryllium, TotalBromoformChlorobenzeneCyanideCadmiumCarbon TetrachlorideChromiumDichloromethaneEthylbenzeneLassoLeadMercuryMonobromoacetic AcidMonochloroacetic AcidNitriteSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
SOMMER, JEFF
Phone
419-628-3377
Email
[email protected]

Frequently asked questions about West Lake Village Mhp

Is West Lake Village Mhp tap water safe to drink?

EPA monitoring detected 16 contaminants in West Lake Village Mhp's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in West Lake Village Mhp's water?

EPA monitoring detected Lead, Bromodichloromethane, Chloroform, Arsenic, Dibromochloromethane, and others. The full list with the level and data source for each is above.

How many people does West Lake Village Mhp serve?

West Lake Village Mhp reports serving 83 people in Ohio, per its EPA record.

Has West Lake Village Mhp had any water quality violations?

The EPA has 87 violations on file for West Lake Village Mhp, of which 20 are health-based (a contaminant limit or required treatment was breached) and 1 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.