← Ohio

Tap water quality report

Payne Village

EPA monitoring tested this supplier for 54 contaminants and detected 19. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

54
contaminants tested
19
detected
1,550
people served
4
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Paulding

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

4
health-based violations
215
violations on file
3
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 1992-12-01 → 1992-12-31
MCL Health-based Resolved 1992-12-01 → 1992-12-31
MCL Health-based Resolved 1992-12-01 → 1992-12-31
MCL Health-based Resolved 1992-12-01 → 1992-12-31
Other Monitoring Unaddressed 2024-11-14
Other Monitoring Unaddressed 2020-02-10
Other Monitoring Unaddressed 2018-11-29
MR Monitoring Resolved 2013-01-01 → 2013-09-30
MR Monitoring Resolved 2013-01-01 → 2013-09-30
MR Monitoring Resolved 2013-01-01 → 2013-09-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
329.2 µg/L 25%
of the EPA limit 1300 µg/L
worst single sample: 385 µg/L
29/40 SYR4 2013–2019
Lead
0.0040 mg/L 27%
of the EPA limit 0.0150 mg/L
20/20 LCR 2025
Nitrate
620 µg/L 6.2%
of the EPA limit 10000 µg/L
16/18 SYR4 2012–2019
Chloroform
7.355 µg/L
No EPA limit set
worst single sample: 8.3 µg/L
10/13 SYR4 2013–2019
Nitrate-Nitrite
609.5 µg/L 6.1%
of the EPA limit 10000 µg/L
worst single sample: 620 µg/L
8/9 SYR4 2012–2019
Bromodichloromethane
6.36 µg/L
No EPA limit set
worst single sample: 6.9 µg/L
7/13 SYR4 2013–2019
Dichloroacetic Acid
4.86 µg/L
No EPA limit set
worst single sample: 5.7 µg/L
7/13 SYR4 2013–2019
TTHM
19.925 µg/L 25%
of the EPA limit 80 µg/L
worst single sample: 21.3 µg/L
6/13 SYR4 2013–2019
Dibromoacetic Acid
3.645 µg/L
No EPA limit set
worst single sample: 3.9 µg/L
4/13 SYR4 2013–2019
Dibromochloromethane
4.42 µg/L
No EPA limit set
worst single sample: 4.6 µg/L
4/13 SYR4 2013–2019
Barium
72.87 µg/L 3.6%
of the EPA limit 2000 µg/L
worst single sample: 73.2 µg/L
3/3 SYR4 2013–2019
Fluoride
1107 µg/L 28%
of the EPA limit 4000 µg/L
worst single sample: 1110 µg/L
3/3 SYR4 2013–2019
Lead
9.56 µg/L 64%
of the EPA limit 15 µg/L
worst single sample: 9.9 µg/L
3/40 SYR4 2013–2019
Total Haloacetic Acids (HAA5)
8.25 µg/L 14%
of the EPA limit 60 µg/L
worst single sample: 8.4 µg/L
3/13 SYR4 2013–2019
Trichloroacetic Acid
2.57 µg/L
No EPA limit set
worst single sample: 2.7 µg/L
3/13 SYR4 2013–2019
Bromoform
1.48 µg/L
No EPA limit set
worst single sample: 1.5 µg/L
2/13 SYR4 2013–2019
Cyanide
14.9 µg/L 7.5%
of the EPA limit 200 µg/L
1/3 SYR4 2013–2019
Combined Radium (-226 And -228)
1.4 pCi/L 28%
of the EPA limit 5 pCi/L
1/1 SYR4 2019
Nitrite
150 µg/L 15%
of the EPA limit 1000 µg/L
1/7 SYR4 2012–2017
35 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-DichloropropaneAntimony, TotalArsenicAsbestosAtrazineBenzeneBeryllium, TotalChlorobenzeneCadmiumCarbon TetrachlorideChromiumDichloromethaneEthylbenzeneLassoMercuryMonobromoacetic AcidMonochloroacetic AcidSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
CHILDS, JARROD
Phone
419-263-2514
Email
[email protected]

Frequently asked questions about Payne Village

Is Payne Village tap water safe to drink?

EPA monitoring detected 19 contaminants in Payne Village's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Payne Village's water?

EPA monitoring detected Copper, Lead, Nitrate, Chloroform, Nitrate-Nitrite, and others. The full list with the level and data source for each is above.

How many people does Payne Village serve?

Payne Village reports serving 1,550 people in Ohio, per its EPA record.

Has Payne Village had any water quality violations?

The EPA has 215 violations on file for Payne Village, of which 4 are health-based (a contaminant limit or required treatment was breached) and 3 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.