Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| Other | Monitoring | Unaddressed | 2018-11-07 |
| MR | Monitoring | Resolved | 2011-04-01 → 2011-04-30 |
| MR | Monitoring | Resolved | 2011-04-01 → 2011-04-30 |
| MR | Monitoring | Resolved | 2011-04-01 → 2011-04-30 |
| MR | Monitoring | Resolved | 2011-04-01 → 2011-04-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 110 µg/L 8.5% of the EPA limit 1300 µg/L
worst single sample: 150 µg/L | 50/64 | SYR4 | 2012–2017 |
| Bromodichloromethane | 11.59 µg/L No EPA limit set
worst single sample: 13.4 µg/L | 38/38 | SYR4 | 2012–2019 |
| Chloroform | 8.75 µg/L No EPA limit set
worst single sample: 10.9 µg/L | 38/38 | SYR4 | 2012–2019 |
| TTHM | 39.18 µg/L 49% of the EPA limit 80 µg/L
worst single sample: 44.8 µg/L | 38/38 | SYR4 | 2012–2019 |
| Dibromochloromethane | 11.78 µg/L No EPA limit set
worst single sample: 13.9 µg/L | 35/38 | SYR4 | 2012–2019 |
| Bromoform | 6.66 µg/L No EPA limit set
worst single sample: 7.2 µg/L | 29/38 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 3.327 µg/L No EPA limit set
worst single sample: 3.93 µg/L | 24/37 | SYR4 | 2012–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 23/23 | LCR | 2025 |
| Dichloroacetic Acid | 3.88 µg/L No EPA limit set
worst single sample: 4.06 µg/L | 16/37 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 17.275 µg/L 29% of the EPA limit 60 µg/L
worst single sample: 18.4 µg/L | 16/37 | SYR4 | 2012–2019 |
| Lead | 8.45 µg/L 56% of the EPA limit 15 µg/L
worst single sample: 9.5 µg/L | 7/64 | SYR4 | 2012–2017 |
| Fluoride | 982.5 µg/L 25% of the EPA limit 4000 µg/L
worst single sample: 992 µg/L | 3/3 | SYR4 | 2012–2018 |
| Monobromoacetic Acid | 1.482 µg/L No EPA limit set
worst single sample: 1.49 µg/L | 3/37 | SYR4 | 2012–2019 |
| Barium | 21.8 µg/L 1.1% of the EPA limit 2000 µg/L
worst single sample: 22 µg/L | 2/3 | SYR4 | 2012–2018 |
| Monochloroacetic Acid | 8.2115 µg/L No EPA limit set
worst single sample: 8.24 µg/L | 2/37 | SYR4 | 2012–2019 |
| Nitrate | 550 µg/L 5.5% of the EPA limit 10000 µg/L | 2/16 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 550 µg/L 5.5% of the EPA limit 10000 µg/L | 1/7 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 1.21 µg/L No EPA limit set | 1/37 | SYR4 | 2012–2019 |
64 contaminants tested, none detected
Utility contact
Frequently asked questions about Wadsworth City
Is Wadsworth City tap water safe to drink?
EPA monitoring detected 18 contaminants in Wadsworth City's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Wadsworth City's water?
EPA monitoring detected Copper, Bromodichloromethane, Chloroform, TTHM, Dibromochloromethane, and others. The full list with the level and data source for each is above.
How many people does Wadsworth City serve?
Wadsworth City reports serving 24,356 people in Ohio, per its EPA record.
Has Wadsworth City had any water quality violations?
The EPA has 5 violations on file for Wadsworth City, of which 0 are health-based (a contaminant limit or required treatment was breached) and 1 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.