← Ohio

Tap water quality report

Toledo City of

EPA monitoring tested this supplier for 97 contaminants and detected 22. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

97
contaminants tested
22
detected
360,000
people served
12
health-based violations
Water source
Surface water
Ownership
Local government
Counties served
Lucas

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

12
health-based violations
27
violations on file
0
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 2023-03-01 → 2023-03-31
TT Health-based Resolved 2023-03-01 → 2023-03-31
TT Health-based Resolved 2023-03-01 → 2023-03-31
TT Health-based Resolved 2023-03-01 → 2023-03-31
TT Health-based Resolved 2015-03-01 → 2015-03-31
TT Health-based Resolved 2015-03-01 → 2015-03-31
TT Health-based Resolved 2015-03-01 → 2015-03-31
TT Health-based Resolved 2015-03-01 → 2015-03-31
MCL Health-based Resolved 2014-04-01 → 2014-06-30
MCL Health-based Resolved 2014-04-01 → 2014-06-30

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
Pfba 0.0050 µg/L 1/4 2025

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Bromodichloromethane
14.4 µg/L
No EPA limit set
worst single sample: 18.5 µg/L
386/386 SYR4 2012–2019
Chloroform
70.05 µg/L
No EPA limit set
worst single sample: 79.7 µg/L
386/386 SYR4 2012–2019
Dibromochloromethane
9.375 µg/L
No EPA limit set
worst single sample: 14.2 µg/L
386/386 SYR4 2012–2019
Dichloroacetic Acid
21.285 µg/L
No EPA limit set
worst single sample: 27.9 µg/L
384/384 SYR4 2012–2019
TTHM
86.98 µg/L 109%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 105.2 µg/L
384/384 SYR4 2012–2019
Dibromoacetic Acid
5 µg/L
No EPA limit set
worst single sample: 6.2 µg/L
378/384 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
27.7 µg/L 46%
of the EPA limit 60 µg/L
worst single sample: 34.1 µg/L
373/384 SYR4 2012–2019
Bromoform
3.4 µg/L
No EPA limit set
worst single sample: 5.6 µg/L
347/386 SYR4 2012–2019
Trichloroacetic Acid
5 µg/L
No EPA limit set
worst single sample: 6.9 µg/L
241/384 SYR4 2012–2019
Nitrate
2925 µg/L 29%
of the EPA limit 10000 µg/L
worst single sample: 4350 µg/L
156/194 SYR4 2012–2019
Copper
17 µg/L 1.3%
of the EPA limit 1300 µg/L
worst single sample: 32 µg/L
125/203 SYR4 2014–2019
Nitrate-Nitrite
2899 µg/L 29%
of the EPA limit 10000 µg/L
worst single sample: 4350 µg/L
78/97 SYR4 2012–2019
Monochloroacetic Acid
3.48 µg/L
No EPA limit set
worst single sample: 5.4 µg/L
34/384 SYR4 2012–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
26/26 LCR 2025
Lead
14.85 µg/L 99%
of the EPA limit 15 µg/L
worst single sample: 18 µg/L
10/203 SYR4 2014–2019
Fluoride
1059 µg/L 26%
of the EPA limit 4000 µg/L
worst single sample: 1080 µg/L
8/8 SYR4 2012–2019
Atrazine
0.2700 µg/L 9%
of the EPA limit 3 µg/L
worst single sample: 0.3000 µg/L
6/26 SYR4 2012–2019
Monobromoacetic Acid
2.08 µg/L
No EPA limit set
worst single sample: 2.1 µg/L
3/384 SYR4 2012–2019
Barium
10 µg/L 0.5%
of the EPA limit 2000 µg/L
1/8 SYR4 2012–2019
Nitrite
10 µg/L 1%
of the EPA limit 1000 µg/L
1/94 SYR4 2012–2019
Simazine
0.0600 µg/L 1.5%
of the EPA limit 4 µg/L
1/26 SYR4 2012–2019
75 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalArsenicBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChromiumCombined Radium (-226 And -228)DichloromethaneDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDiquatEndothallEthylbenzeneGlyphosateGross Beta Particle ActivityHfpo-DaLassoMercuryMethoxychlorNetfosaaNfdhaNmefosaaOxamylPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSeleniumStyreneTetrachloroethyleneThallium, TotalTolueneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
BANNISTER, PATEKKA
Phone
419-245-1846
Email
[email protected]

Frequently asked questions about Toledo City of

Is Toledo City of tap water safe to drink?

EPA monitoring detected 22 contaminants in Toledo City of's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Toledo City of's water?

EPA monitoring detected Bromodichloromethane, Chloroform, Dibromochloromethane, Dichloroacetic Acid, TTHM, and others. The full list with the level and data source for each is above.

How many people does Toledo City of serve?

Toledo City of reports serving 360,000 people in Ohio, per its EPA record.

Has Toledo City of had any water quality violations?

The EPA has 27 violations on file for Toledo City of, of which 12 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.