Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2018-04-01 → 2018-06-30 |
| MCL | Health-based | Resolved | 2018-04-01 → 2018-06-30 |
| MCL | Health-based | Resolved | 2018-04-01 → 2018-06-30 |
| MCL | Health-based | Resolved | 2018-04-01 → 2018-06-30 |
| MCL | Health-based | Resolved | 2018-04-01 → 2018-06-30 |
| MCL | Health-based | Resolved | 2018-01-01 → 2018-03-31 |
| MCL | Health-based | Resolved | 2018-01-01 → 2018-03-31 |
| MCL | Health-based | Resolved | 2018-01-01 → 2018-03-31 |
| MCL | Health-based | Resolved | 2018-01-01 → 2018-03-31 |
| MCL | Health-based | Resolved | 2018-01-01 → 2018-03-31 |
PFAS detected
| Contaminant | Max | Detection rate | Period |
|---|---|---|---|
| Pfba | 0.0076 µg/L | 1/4 | 2025 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 4337.5 µg/L 43% of the EPA limit 10000 µg/L
worst single sample: 5400 µg/L | 158/194 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 4325 µg/L 43% of the EPA limit 10000 µg/L
worst single sample: 5400 µg/L | 79/97 | SYR4 | 2012–2019 |
| Bromodichloromethane | 20.77 µg/L No EPA limit set
worst single sample: 22.9 µg/L | 60/60 | SYR4 | 2012–2019 |
| Chloroform | 85.13 µg/L No EPA limit set
worst single sample: 93.5 µg/L | 60/60 | SYR4 | 2012–2019 |
| Dibromochloromethane | 8.505 µg/L No EPA limit set
worst single sample: 9.3 µg/L | 60/60 | SYR4 | 2012–2019 |
| TTHM | 112.295 µg/L 140% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 121 µg/L | 60/60 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 35.25 µg/L 59% of the EPA limit 60 µg/L
worst single sample: 40.6 µg/L | 60/60 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 6.825 µg/L No EPA limit set
worst single sample: 27.8 µg/L | 60/60 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 23.62 µg/L No EPA limit set
worst single sample: 26.9 µg/L | 59/60 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 3.13 µg/L No EPA limit set
worst single sample: 5.4 µg/L | 55/60 | SYR4 | 2012–2019 |
| Bromoform | 1.035 µg/L No EPA limit set
worst single sample: 1.3 µg/L | 34/60 | SYR4 | 2012–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 19/19 | LCR | 2025 |
| Monochloroacetic Acid | 4.52 µg/L No EPA limit set
worst single sample: 5.5 µg/L | 15/60 | SYR4 | 2012–2019 |
| Fluoride | 929.5 µg/L 23% of the EPA limit 4000 µg/L
worst single sample: 940 µg/L | 8/8 | SYR4 | 2012–2019 |
| Copper | 553.6 µg/L 43% of the EPA limit 1300 µg/L
worst single sample: 657 µg/L | 5/41 | SYR4 | 2014–2017 |
| Lead | 41.58 µg/L 277% of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 43.7 µg/L | 3/41 | SYR4 | 2014–2017 |
| Monobromoacetic Acid | 2.28 µg/L No EPA limit set
worst single sample: 2.3 µg/L | 3/60 | SYR4 | 2012–2019 |
| Barium | 11 µg/L 0.5% of the EPA limit 2000 µg/L | 1/8 | SYR4 | 2012–2019 |
68 contaminants tested, none detected
Utility contact
Frequently asked questions about Bellevue City
Is Bellevue City tap water safe to drink?
EPA monitoring detected 19 contaminants in Bellevue City's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Bellevue City's water?
EPA monitoring detected Nitrate, Nitrate-Nitrite, Bromodichloromethane, Chloroform, Dibromochloromethane, and others. The full list with the level and data source for each is above.
How many people does Bellevue City serve?
Bellevue City reports serving 8,236 people in Ohio, per its EPA record.
Has Bellevue City had any water quality violations?
The EPA has 51 violations on file for Bellevue City, of which 23 are health-based (a contaminant limit or required treatment was breached) and 2 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.