← Ohio

Tap water quality report

Millersburg Village

EPA monitoring tested this supplier for 86 contaminants and detected 15. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

86
contaminants tested
15
detected
3,151
people served
10
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Holmes

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

10
health-based violations
11
violations on file
1
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 1993-08-01 → 1993-08-31
MCL Health-based Resolved 1993-08-01 → 1993-08-31
MCL Health-based Resolved 1993-08-01 → 1993-08-31
MCL Health-based Resolved 1993-08-01 → 1993-08-31
MCL Health-based Resolved 1993-08-01 → 1993-08-31
MCL Health-based Resolved 1993-08-01 → 1993-08-31
MCL Health-based Resolved 1993-08-01 → 1993-08-31
MCL Health-based Resolved 1993-08-01 → 1993-08-31
MCL Health-based Resolved 1993-08-01 → 1993-08-31
MCL Health-based Resolved 1993-08-01 → 1993-08-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
813.6 µg/L 63%
of the EPA limit 1300 µg/L
worst single sample: 913 µg/L
23/30 SYR4 2014–2018
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
20/20 LCR 2025
Nitrate
1080 µg/L 11%
of the EPA limit 10000 µg/L
16/16 SYR4 2012–2019
Bromodichloromethane
5.239 µg/L
No EPA limit set
worst single sample: 5.33 µg/L
15/15 SYR4 2012–2019
Bromoform
4.842 µg/L
No EPA limit set
worst single sample: 4.94 µg/L
15/15 SYR4 2012–2019
Dibromochloromethane
7.381 µg/L
No EPA limit set
worst single sample: 8.27 µg/L
15/15 SYR4 2012–2019
TTHM
23.76 µg/L 30%
of the EPA limit 80 µg/L
worst single sample: 24.6 µg/L
15/15 SYR4 2012–2019
Chloroform
8.394 µg/L
No EPA limit set
worst single sample: 9.19 µg/L
9/15 SYR4 2012–2019
Dibromoacetic Acid
2.76 µg/L
No EPA limit set
worst single sample: 2.8 µg/L
9/15 SYR4 2012–2019
Nitrate-Nitrite
1080 µg/L 11%
of the EPA limit 10000 µg/L
8/8 SYR4 2012–2019
Dichloroacetic Acid
1.67 µg/L
No EPA limit set
worst single sample: 1.7 µg/L
4/15 SYR4 2012–2019
Barium
86.02 µg/L 4.3%
of the EPA limit 2000 µg/L
worst single sample: 86.3 µg/L
3/3 SYR4 2012–2018
Monobromoacetic Acid
1.9 µg/L
No EPA limit set
2/15 SYR4 2012–2019
Gross Alpha, Excl. Radon And U
15.2 pCi/L 101%
of the EPA limit, at the 95th percentile of samples — 15 pCi/L
1/1 SYR4 2015
Trichloroacetic Acid
1.7 µg/L
No EPA limit set
1/15 SYR4 2012–2019
71 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalArsenicAsbestosAtrazineBenzeneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbon TetrachlorideChromiumCombined Radium (-226 And -228)Combined UraniumDichloromethaneEthylbenzeneFluorideHfpo-DaLassoLeadMercuryMonochloroacetic AcidNetfosaaNfdhaNmefosaaNitritePfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Haloacetic Acids (HAA5)TrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
TROYER, NATHAN
Phone
330-674-1886
Email
[email protected]

Frequently asked questions about Millersburg Village

Is Millersburg Village tap water safe to drink?

EPA monitoring detected 15 contaminants in Millersburg Village's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Millersburg Village's water?

EPA monitoring detected Copper, Lead, Nitrate, Bromodichloromethane, Bromoform, and others. The full list with the level and data source for each is above.

How many people does Millersburg Village serve?

Millersburg Village reports serving 3,151 people in Ohio, per its EPA record.

Has Millersburg Village had any water quality violations?

The EPA has 11 violations on file for Millersburg Village, of which 10 are health-based (a contaminant limit or required treatment was breached) and 1 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.