EPA monitoring tested this supplier for 80 contaminants and detected 19. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

80
contaminants tested
19
detected
10,520
people served
376
health-based violations
Water source
Surface water
Ownership
Local government
Counties served
Guernsey

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

376
health-based violations
481
violations on file
1
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 2019-06-01 → 2019-06-30
TT Health-based Resolved 2019-06-01 → 2019-06-30
TT Health-based Resolved 2019-06-01 → 2019-06-30
TT Health-based Resolved 2019-06-01 → 2019-06-30
MCL Health-based Resolved 2017-01-01 → 2017-03-31
MCL Health-based Resolved 2017-01-01 → 2017-03-31
MCL Health-based Resolved 2017-01-01 → 2017-03-31
MCL Health-based Resolved 2017-01-01 → 2017-03-31
MCL Health-based Resolved 2016-07-01 → 2016-09-30
MCL Health-based Resolved 2016-07-01 → 2016-09-30

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
PFOA 0.0056 µg/L 4/4 2025
Pfba 0.0054 µg/L 1/4 2025

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate
760 µg/L 7.6%
of the EPA limit 10000 µg/L
worst single sample: 4700 µg/L
166/190 SYR4 2012–2019
Bromodichloromethane
22.8 µg/L
No EPA limit set
worst single sample: 28.8 µg/L
131/131 SYR4 2012–2019
Chloroform
69.75 µg/L
No EPA limit set
worst single sample: 80.8 µg/L
131/131 SYR4 2012–2019
TTHM
90.98 µg/L 114%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 109.9 µg/L
129/129 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
54.86 µg/L 91%
of the EPA limit 60 µg/L
worst single sample: 64.4 µg/L
129/129 SYR4 2012–2019
Dichloroacetic Acid
24.83 µg/L
No EPA limit set
worst single sample: 32.9 µg/L
128/129 SYR4 2012–2019
Trichloroacetic Acid
31.89 µg/L
No EPA limit set
worst single sample: 40.9 µg/L
128/129 SYR4 2012–2019
Dibromochloromethane
6.198 µg/L
No EPA limit set
worst single sample: 7.07 µg/L
127/131 SYR4 2012–2019
Copper
88.7 µg/L 6.8%
of the EPA limit 1300 µg/L
worst single sample: 118 µg/L
43/435 SYR4 2012–2019
Monochloroacetic Acid
4.16 µg/L
No EPA limit set
worst single sample: 4.6 µg/L
33/129 SYR4 2012–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
24/24 LCR 2025
Dibromoacetic Acid
6.16 µg/L
No EPA limit set
worst single sample: 6.7 µg/L
19/128 SYR4 2012–2019
Bromoform
0.8975 µg/L
No EPA limit set
worst single sample: 0.9500 µg/L
16/130 SYR4 2012–2019
Lead
8.85 µg/L 59%
of the EPA limit 15 µg/L
worst single sample: 12 µg/L
10/90 SYR4 2014–2018
Fluoride
1146 µg/L 29%
of the EPA limit 4000 µg/L
worst single sample: 1170 µg/L
9/9 SYR4 2012–2019
Barium
31 µg/L 1.6%
of the EPA limit 2000 µg/L
1/9 SYR4 2012–2019
Chromium
1.28 µg/L 1.3%
of the EPA limit 100 µg/L
1/9 SYR4 2012–2019
61 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalArsenicAtrazineBenzeneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbon TetrachlorideDichloromethaneEthylbenzeneHfpo-DaLassoMercuryMonobromoacetic AcidNetfosaaNfdhaNmefosaaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOSPfpeaPfpesPftaPftrdaPfunaSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
ORR, TOM D.
Phone
740-432-7584
Email
[email protected]

Frequently asked questions about Cambridge, City of

Is Cambridge, City of tap water safe to drink?

EPA monitoring detected 19 contaminants in Cambridge, City of's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Cambridge, City of's water?

EPA monitoring detected Nitrate, Bromodichloromethane, Chloroform, TTHM, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.

How many people does Cambridge, City of serve?

Cambridge, City of reports serving 10,520 people in Ohio, per its EPA record.

Has Cambridge, City of had any water quality violations?

The EPA has 481 violations on file for Cambridge, City of, of which 376 are health-based (a contaminant limit or required treatment was breached) and 1 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.