← Ohio

Tap water quality report

Aqua Ohio - Worthington Hills

EPA monitoring tested this supplier for 62 contaminants and detected 16. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

62
contaminants tested
16
detected
2,500
people served
0
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Franklin

Compliance record

No violations on file. The EPA has no formal drinking-water violations recorded for this supplier.

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
410 µg/L 32%
of the EPA limit 1300 µg/L
worst single sample: 600 µg/L
20/20 SYR4 2014–2017
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
19/19 LCR 2025
Bromodichloromethane
16.555 µg/L
No EPA limit set
worst single sample: 18.7 µg/L
14/14 SYR4 2013–2019
Bromoform
6.01 µg/L
No EPA limit set
worst single sample: 6.4 µg/L
14/14 SYR4 2013–2019
Chloroform
9.705 µg/L
No EPA limit set
worst single sample: 11.2 µg/L
14/14 SYR4 2013–2019
Dibromochloromethane
17.6 µg/L
No EPA limit set
worst single sample: 18.9 µg/L
14/14 SYR4 2013–2019
TTHM
49.87 µg/L 62%
of the EPA limit 80 µg/L
worst single sample: 55.2 µg/L
14/14 SYR4 2013–2019
Total Haloacetic Acids (HAA5)
9.06 µg/L 15%
of the EPA limit 60 µg/L
worst single sample: 9.2 µg/L
8/14 SYR4 2013–2019
Dichloroacetic Acid
3.17 µg/L
No EPA limit set
worst single sample: 3.2 µg/L
7/14 SYR4 2013–2019
Dibromoacetic Acid
4.34 µg/L
No EPA limit set
worst single sample: 4.4 µg/L
5/14 SYR4 2013–2019
Barium
63 µg/L 3.2%
of the EPA limit 2000 µg/L
worst single sample: 65 µg/L
2/2 SYR4 2014–2017
Fluoride
1037.25 µg/L 26%
of the EPA limit 4000 µg/L
worst single sample: 1040 µg/L
2/2 SYR4 2014–2017
Nitrate
50 µg/L 0.5%
of the EPA limit 10000 µg/L
2/16 SYR4 2012–2019
Trichloroacetic Acid
1.6 µg/L
No EPA limit set
2/14 SYR4 2013–2019
Lead
15 µg/L 100%
of the EPA limit 15 µg/L
1/20 SYR4 2014–2017
Monochloroacetic Acid
3.2 µg/L
No EPA limit set
1/14 SYR4 2013–2019
46 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-DichloropropaneAntimony, TotalArsenicAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbon TetrachlorideChromiumDichloromethaneDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateEndrinEthylbenzeneHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidNitrate-NitriteNitriteSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
DUNN, DAVID
Phone
614-882-6586
Email
[email protected]

Frequently asked questions about Aqua Ohio - Worthington Hills

Is Aqua Ohio - Worthington Hills tap water safe to drink?

EPA monitoring detected 16 contaminants in Aqua Ohio - Worthington Hills's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Aqua Ohio - Worthington Hills's water?

EPA monitoring detected Copper, Lead, Bromodichloromethane, Bromoform, Chloroform, and others. The full list with the level and data source for each is above.

How many people does Aqua Ohio - Worthington Hills serve?

Aqua Ohio - Worthington Hills reports serving 2,500 people in Ohio, per its EPA record.

Has Aqua Ohio - Worthington Hills had any water quality violations?

The EPA has no formal drinking-water violations on file for Aqua Ohio - Worthington Hills.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.