← Ohio

Tap water quality report

Gahanna City

EPA monitoring tested this supplier for 44 contaminants and detected 13. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

44
contaminants tested
13
detected
33,258
people served
12
health-based violations
Water source
SWP
Ownership
Local government
Counties served
Franklin

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

12
health-based violations
33
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2013-04-01 → 2013-06-30
MCL Health-based Resolved 2013-04-01 → 2013-06-30
MCL Health-based Resolved 2013-04-01 → 2013-06-30
MCL Health-based Resolved 2013-04-01 → 2013-06-30
MCL Health-based Resolved 2013-01-01 → 2013-03-31
MCL Health-based Resolved 2013-01-01 → 2013-03-31
MCL Health-based Resolved 2013-01-01 → 2013-03-31
MCL Health-based Resolved 2013-01-01 → 2013-03-31
MCL Health-based Resolved 2012-10-01 → 2012-12-31
MCL Health-based Resolved 2012-10-01 → 2012-12-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Bromodichloromethane
13.965 µg/L
No EPA limit set
worst single sample: 19.3 µg/L
128/128 SYR4 2012–2019
Chloroform
70.665 µg/L
No EPA limit set
worst single sample: 88.6 µg/L
128/128 SYR4 2012–2019
Dichloroacetic Acid
29.465 µg/L
No EPA limit set
worst single sample: 37 µg/L
128/128 SYR4 2012–2019
TTHM
89.32 µg/L 112%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 110 µg/L
128/128 SYR4 2012–2019
Dibromochloromethane
3.4 µg/L
No EPA limit set
worst single sample: 6.3 µg/L
127/128 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
53.26 µg/L 89%
of the EPA limit 60 µg/L
worst single sample: 63.4 µg/L
125/128 SYR4 2012–2019
Trichloroacetic Acid
24.24 µg/L
No EPA limit set
worst single sample: 28.4 µg/L
125/128 SYR4 2012–2019
Monochloroacetic Acid
7.64 µg/L
No EPA limit set
worst single sample: 13.6 µg/L
117/128 SYR4 2012–2019
Bromoform
2.065 µg/L
No EPA limit set
worst single sample: 3.1 µg/L
48/128 SYR4 2012–2019
Copper
83.8 µg/L 6.4%
of the EPA limit 1300 µg/L
worst single sample: 124 µg/L
25/100 SYR4 2012–2018
Lead
0.00050 mg/L 3.3%
of the EPA limit 0.0150 mg/L
22/22 LCR 2024
Lead
24.305 µg/L 162%
of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 25.1 µg/L
2/99 SYR4 2012–2018
Dibromoacetic Acid
1.2 µg/L
No EPA limit set
1/128 SYR4 2012–2019
31 contaminants tested, none detected
11Cl-PF3OUdS4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaHfpo-DaMonobromoacetic AcidNetfosaaNfdhaNmefosaaPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaLithium

Utility contact

Contact
JONES, MATTHEW D
Phone
614-342-4427
Email
[email protected]

Frequently asked questions about Gahanna City

Is Gahanna City tap water safe to drink?

EPA monitoring detected 13 contaminants in Gahanna City's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Gahanna City's water?

EPA monitoring detected Bromodichloromethane, Chloroform, Dichloroacetic Acid, TTHM, Dibromochloromethane, and others. The full list with the level and data source for each is above.

How many people does Gahanna City serve?

Gahanna City reports serving 33,258 people in Ohio, per its EPA record.

Has Gahanna City had any water quality violations?

The EPA has 33 violations on file for Gahanna City, of which 12 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.