Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2018-10-01 → 2018-12-31 |
| MCL | Health-based | Resolved | 2018-10-01 → 2018-12-31 |
| MCL | Health-based | Resolved | 2018-10-01 → 2018-12-31 |
| MCL | Health-based | Resolved | 2018-10-01 → 2018-12-31 |
| MCL | Health-based | Resolved | 1996-11-01 → 1996-11-30 |
| MCL | Health-based | Resolved | 1996-11-01 → 1996-11-30 |
| MCL | Health-based | Resolved | 1996-11-01 → 1996-11-30 |
| MCL | Health-based | Resolved | 1996-11-01 → 1996-11-30 |
| MCL | Health-based | Resolved | 1996-11-01 → 1996-11-30 |
| Other | Monitoring | Resolved | 2024-07-31 |
PFAS detected
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 1886.5 µg/L 19% of the EPA limit 10000 µg/L
worst single sample: 4350 µg/L | 304/346 | SYR4 | 2012–2019 |
| Bromodichloromethane | 16.415 µg/L No EPA limit set
worst single sample: 21.4 µg/L | 258/258 | SYR4 | 2012–2019 |
| Chloroform | 79.91 µg/L No EPA limit set
worst single sample: 134 µg/L | 258/258 | SYR4 | 2012–2019 |
| TTHM | 97.845 µg/L 122% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 155 µg/L | 258/258 | SYR4 | 2012–2019 |
| Dibromochloromethane | 8.994 µg/L No EPA limit set
worst single sample: 13.6 µg/L | 257/258 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 28.96 µg/L No EPA limit set
worst single sample: 40.7 µg/L | 229/257 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 55 µg/L 92% of the EPA limit 60 µg/L
worst single sample: 71.9 µg/L | 215/256 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 28.31 µg/L No EPA limit set
worst single sample: 40.7 µg/L | 214/256 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 1846 µg/L 18% of the EPA limit 10000 µg/L
worst single sample: 4350 µg/L | 153/176 | SYR4 | 2012–2019 |
| Bromoform | 3.606 µg/L No EPA limit set
worst single sample: 6.06 µg/L | 113/258 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 3.305 µg/L No EPA limit set
worst single sample: 4.1 µg/L | 100/256 | SYR4 | 2012–2019 |
| Copper | 448.1 µg/L 34% of the EPA limit 1300 µg/L
worst single sample: 647 µg/L | 95/102 | SYR4 | 2014–2017 |
| Fluoride | 1178 µg/L 29% of the EPA limit 4000 µg/L
worst single sample: 1190 µg/L | 24/24 | SYR4 | 2012–2019 |
| Lead | 0.0021 mg/L 14% of the EPA limit 0.0150 mg/L | 20/20 | LCR | 2023 |
| Barium | 41.81 µg/L 2.1% of the EPA limit 2000 µg/L
worst single sample: 49.1 µg/L | 19/24 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 28.74 µg/L No EPA limit set
worst single sample: 30 µg/L | 15/257 | SYR4 | 2012–2019 |
| Lead | 14.18 µg/L 95% of the EPA limit 15 µg/L
worst single sample: 14.6 µg/L | 4/102 | SYR4 | 2014–2017 |
| Atrazine | 2.62 µg/L 87% of the EPA limit 3 µg/L
worst single sample: 2.8 µg/L | 3/23 | SYR4 | 2012–2019 |
| Simazine | 0.2080 µg/L 5.2% of the EPA limit 4 µg/L
worst single sample: 0.2100 µg/L | 3/23 | SYR4 | 2012–2019 |
| Arsenic | 3.6 µg/L 36% of the EPA limit 10 µg/L | 1/24 | SYR4 | 2012–2019 |
| Nitrite | 10 µg/L 1% of the EPA limit 1000 µg/L | 1/109 | SYR4 | 2012–2018 |
59 contaminants tested, none detected
Utility contact
Frequently asked questions about Clermont Public Water
Is Clermont Public Water tap water safe to drink?
EPA monitoring detected 24 contaminants in Clermont Public Water's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Clermont Public Water's water?
EPA monitoring detected Nitrate, Bromodichloromethane, Chloroform, TTHM, Dibromochloromethane, and others. The full list with the level and data source for each is above.
How many people does Clermont Public Water serve?
Clermont Public Water reports serving 133,059 people in Ohio, per its EPA record.
Has Clermont Public Water had any water quality violations?
The EPA has 57 violations on file for Clermont Public Water, of which 9 are health-based (a contaminant limit or required treatment was breached) and 2 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.