Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| RPT | Monitoring | Resolved | 2024-10-17 |
| RPT | Monitoring | Resolved | 2024-10-17 |
| RPT | Monitoring | Resolved | 2024-10-17 |
| MON | Monitoring | Archived | 2024-03-01 → 2024-03-31 |
| MON | Monitoring | Archived | 2024-03-01 → 2024-03-31 |
| MR | Monitoring | Resolved | 2023-01-01 → 2023-12-31 |
| MR | Monitoring | Resolved | 2023-01-01 → 2023-12-31 |
| MR | Monitoring | Resolved | 2023-01-01 → 2023-12-31 |
| MR | Monitoring | Resolved | 2023-01-01 → 2023-12-31 |
| MR | Monitoring | Resolved | 2023-01-01 → 2023-12-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Lead | 0.0038 mg/L 25% of the EPA limit 0.0150 mg/L | 10/10 | LCR | 2024 |
| Nitrate | 130 µg/L 1.3% of the EPA limit 10000 µg/L | 6/16 | SYR4 | 2012–2019 |
| Bromodichloromethane | 1.3085 µg/L No EPA limit set
worst single sample: 1.34 µg/L | 4/4 | SYR4 | 2012–2019 |
| Chloroform | 2.7175 µg/L No EPA limit set
worst single sample: 2.74 µg/L | 4/4 | SYR4 | 2012–2019 |
| Dibromochloromethane | 0.7190 µg/L No EPA limit set
worst single sample: 0.7400 µg/L | 4/4 | SYR4 | 2012–2019 |
| TTHM | 4.6355 µg/L 5.8% of the EPA limit 80 µg/L
worst single sample: 4.67 µg/L | 4/4 | SYR4 | 2012–2019 |
| Barium | 273.2 µg/L 14% of the EPA limit 2000 µg/L
worst single sample: 279 µg/L | 3/3 | SYR4 | 2014–2017 |
| Dichloroacetic Acid | 1.48 µg/L No EPA limit set
worst single sample: 1.5 µg/L | 2/4 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 2.365 µg/L 3.9% of the EPA limit 60 µg/L
worst single sample: 2.4 µg/L | 2/4 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 0.8870 µg/L No EPA limit set
worst single sample: 0.9000 µg/L | 2/4 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 2940 µg/L 29% of the EPA limit 10000 µg/L | 1/1 | SYR4 | 2014 |
59 contaminants tested, none detected
Utility contact
Frequently asked questions about 1610 Llc (Willow Manor Apts)
Is 1610 Llc (Willow Manor Apts) tap water safe to drink?
EPA monitoring detected 11 contaminants in 1610 Llc (Willow Manor Apts)'s water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in 1610 Llc (Willow Manor Apts)'s water?
EPA monitoring detected Lead, Nitrate, Bromodichloromethane, Chloroform, Dibromochloromethane, and others. The full list with the level and data source for each is above.
How many people does 1610 Llc (Willow Manor Apts) serve?
1610 Llc (Willow Manor Apts) reports serving 35 people in Colorado, per its EPA record.
Has 1610 Llc (Willow Manor Apts) had any water quality violations?
The EPA has 704 violations on file for 1610 Llc (Willow Manor Apts), of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.