← New York

Tap water quality report

Watchtower Farms I

EPA monitoring tested this supplier for 71 contaminants and detected 14. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

71
contaminants tested
14
detected
1,800
people served
0
health-based violations
Water source
Surface water
Ownership
Private
Counties served
Ulster

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

0
health-based violations
6
violations on file
0
still open
ViolationTypeStatusPeriod
MR Monitoring Resolved 2008-01-01
MR Monitoring Resolved 2008-01-01
MR Monitoring Resolved 2008-01-01
Other Monitoring Resolved 2001-11-01 → 2001-11-30
MR Monitoring Resolved 1995-10-01
MR Monitoring Resolved 1995-10-01

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Dichloroacetic Acid
19.9 µg/L
No EPA limit set
worst single sample: 29 µg/L
32/32 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
32.45 µg/L 54%
of the EPA limit 60 µg/L
worst single sample: 45 µg/L
32/32 SYR4 2012–2019
Trichloroacetic Acid
17.9 µg/L
No EPA limit set
worst single sample: 23 µg/L
32/32 SYR4 2012–2019
Chloroform
49.75 µg/L
No EPA limit set
worst single sample: 70 µg/L
31/31 SYR4 2012–2019
TTHM
56.3 µg/L 70%
of the EPA limit 80 µg/L
worst single sample: 78 µg/L
31/31 SYR4 2012–2019
Bromodichloromethane
6.975 µg/L
No EPA limit set
worst single sample: 7.3 µg/L
30/31 SYR4 2012–2019
Dibromochloromethane
2.8 µg/L
No EPA limit set
worst single sample: 5.5 µg/L
19/31 SYR4 2012–2019
Lead
0.0014 mg/L 9.3%
of the EPA limit 0.0150 mg/L
10/10 LCR 2023
Barium
5138.85 µg/L 257%
of the EPA limit, at the 95th percentile of samples — 2000 µg/L
worst single sample: 7900 µg/L
8/8 SYR4 2012–2019
Dalapon
1.18 µg/L 0.6%
of the EPA limit 200 µg/L
worst single sample: 1.2 µg/L
5/10 SYR4 2012–2019
Nitrate
80 µg/L 0.8%
of the EPA limit 10000 µg/L
4/16 SYR4 2012–2019
Antimony, Total
0.8300 µg/L 14%
of the EPA limit 6 µg/L
1/8 SYR4 2012–2019
Monobromoacetic Acid
1.91 µg/L
No EPA limit set
1/33 SYR4 2012–2019
Monochloroacetic Acid
2.1 µg/L
No EPA limit set
1/33 SYR4 2012–2019
57 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DArsenicAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalBromoformChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumCombined Radium (-226 And -228)Combined UraniumDichloromethaneDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDibromoacetic AcidDinosebEthylene DibromideEndrinEthylbenzeneFluorideHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorOxamylPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
BRITTAIN, MARTIN
Phone
845-744-6000
Email
[email protected]

Frequently asked questions about Watchtower Farms I

Is Watchtower Farms I tap water safe to drink?

EPA monitoring detected 14 contaminants in Watchtower Farms I's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Watchtower Farms I's water?

EPA monitoring detected Dichloroacetic Acid, Total Haloacetic Acids (HAA5), Trichloroacetic Acid, Chloroform, TTHM, and others. The full list with the level and data source for each is above.

How many people does Watchtower Farms I serve?

Watchtower Farms I reports serving 1,800 people in New York, per its EPA record.

Has Watchtower Farms I had any water quality violations?

The EPA has 6 violations on file for Watchtower Farms I, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.