Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MRDL | Health-based | Resolved | 2020-02-01 → 2020-02-29 |
| MRDL | Health-based | Resolved | 2020-02-01 → 2020-02-29 |
| MRDL | Health-based | Resolved | 2020-02-01 → 2020-02-29 |
| TT | Health-based | Resolved | 2016-07-01 → 2016-07-31 |
| TT | Health-based | Resolved | 2016-07-01 → 2016-07-31 |
| TT | Health-based | Resolved | 2016-07-01 → 2016-07-31 |
| MCL | Health-based | Resolved | 2003-04-01 → 2003-06-30 |
| MCL | Health-based | Resolved | 2003-04-01 → 2003-06-30 |
| MCL | Health-based | Resolved | 2003-04-01 → 2003-06-30 |
| MCL | Health-based | Resolved | 2003-04-01 → 2003-06-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Bromodichloromethane | 16.85 µg/L No EPA limit set
worst single sample: 25 µg/L | 124/124 | SYR4 | 2012–2019 |
| Chloroform | 63.7 µg/L No EPA limit set
worst single sample: 101 µg/L | 124/124 | SYR4 | 2012–2019 |
| TTHM | 81.785 µg/L 102% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 131.3 µg/L | 124/124 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 54.7 µg/L 91% of the EPA limit 60 µg/L
worst single sample: 81.7 µg/L | 123/123 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 35 µg/L No EPA limit set
worst single sample: 43.5 µg/L | 123/123 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 23.9 µg/L No EPA limit set
worst single sample: 35.7 µg/L | 122/123 | SYR4 | 2012–2019 |
| Dibromochloromethane | 4.33 µg/L No EPA limit set
worst single sample: 5.4 µg/L | 119/124 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 5.25 µg/L No EPA limit set
worst single sample: 15 µg/L | 34/124 | SYR4 | 2012–2019 |
| Nitrate | 630 µg/L 6.3% of the EPA limit 10000 µg/L | 18/20 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 2.72 µg/L No EPA limit set
worst single sample: 3.6 µg/L | 17/124 | SYR4 | 2012–2019 |
| Lead | 0.0024 mg/L 16% of the EPA limit 0.0150 mg/L | 15/15 | LCR | 2025 |
| Monobromoacetic Acid | 10.6 µg/L No EPA limit set
worst single sample: 12 µg/L | 15/124 | SYR4 | 2012–2019 |
| Barium | 42.6 µg/L 2.1% of the EPA limit 2000 µg/L
worst single sample: 45 µg/L | 9/10 | SYR4 | 2012–2019 |
| Chromium | 5.7 µg/L 5.7% of the EPA limit 100 µg/L
worst single sample: 6.4 µg/L | 6/9 | SYR4 | 2013–2019 |
| Chlorite | 552.15 µg/L 55% of the EPA limit 1000 µg/L
worst single sample: 588 µg/L | 4/4 | SYR4 | 2018–2019 |
| Fluoride | 190 µg/L 4.8% of the EPA limit 4000 µg/L | 1/10 | SYR4 | 2012–2019 |
85 contaminants tested, none detected
Utility contact
Frequently asked questions about Ithaca City
Is Ithaca City tap water safe to drink?
EPA monitoring detected 16 contaminants in Ithaca City's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Ithaca City's water?
EPA monitoring detected Bromodichloromethane, Chloroform, TTHM, Total Haloacetic Acids (HAA5), Trichloroacetic Acid, and others. The full list with the level and data source for each is above.
How many people does Ithaca City serve?
Ithaca City reports serving 29,457 people in New York, per its EPA record.
Has Ithaca City had any water quality violations?
The EPA has 27 violations on file for Ithaca City, of which 22 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.