| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2022-01-01 → 2022-03-31 |
| MCL | Health-based | Resolved | 2022-01-01 → 2022-03-31 |
| MCL | Health-based | Resolved | 2022-01-01 → 2022-03-31 |
| MCL | Health-based | Resolved | 2022-01-01 → 2022-03-31 |
| MCL | Health-based | Resolved | 2022-01-01 → 2022-03-31 |
| MCL | Health-based | Resolved | 2021-10-01 → 2021-12-31 |
| MCL | Health-based | Resolved | 2021-10-01 → 2021-12-31 |
| MCL | Health-based | Resolved | 2021-10-01 → 2021-12-31 |
| MCL | Health-based | Resolved | 2021-10-01 → 2021-12-31 |
| MCL | Health-based | Resolved | 2021-10-01 → 2021-12-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Bromodichloromethane | 42.65 µg/L No EPA limit set
worst single sample: 46 µg/L | 22/22 | SYR4 | 2014–2019 |
| Bromoform | 11 µg/L No EPA limit set
worst single sample: 12 µg/L | 22/22 | SYR4 | 2014–2019 |
| Chloroform | 28.825 µg/L No EPA limit set
worst single sample: 38 µg/L | 22/22 | SYR4 | 2014–2019 |
| Dibromochloromethane | 47.65 µg/L No EPA limit set
worst single sample: 50 µg/L | 22/22 | SYR4 | 2014–2019 |
| TTHM | 131 µg/L 164% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 144 µg/L | 22/22 | SYR4 | 2014–2019 |
| Dibromoacetic Acid | 9.8 µg/L No EPA limit set
worst single sample: 11 µg/L | 21/22 | SYR4 | 2014–2019 |
| Dichloroacetic Acid | 9.9 µg/L No EPA limit set
worst single sample: 13 µg/L | 21/22 | SYR4 | 2014–2019 |
| Total Haloacetic Acids (HAA5) | 29 µg/L 48% of the EPA limit 60 µg/L | 21/22 | SYR4 | 2014–2019 |
| Trichloroacetic Acid | 6.913 µg/L No EPA limit set
worst single sample: 8.3 µg/L | 20/22 | SYR4 | 2014–2019 |
| Monobromoacetic Acid | 3.279 µg/L No EPA limit set
worst single sample: 3.9 µg/L | 10/22 | SYR4 | 2014–2019 |
| Monochloroacetic Acid | 14.4 µg/L No EPA limit set
worst single sample: 16 µg/L | 9/22 | SYR4 | 2014–2019 |
| Lead | 0.0101 mg/L 68% of the EPA limit 0.0150 mg/L | 7/7 | LCR | 2023 |
Utility contact
Frequently asked questions about Willard Water District
Is Willard Water District tap water safe to drink?
EPA monitoring detected 12 contaminants in Willard Water District's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Willard Water District's water?
EPA monitoring detected Bromodichloromethane, Bromoform, Chloroform, Dibromochloromethane, TTHM, and others. The full list with the level and data source for each is above.
How many people does Willard Water District serve?
Willard Water District reports serving 372 people in New York, per its EPA record.
Has Willard Water District had any water quality violations?
The EPA has 20 violations on file for Willard Water District, of which 10 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.