← New York

Tap water quality report

Brunswick Consolidated Water District

EPA monitoring tested this supplier for 44 contaminants and detected 13. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

44
contaminants tested
13
detected
7,050
people served
18
health-based violations
Water source
SWP
Ownership
Local government
Counties served
Rensselaer

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

18
health-based violations
47
violations on file
5
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2022-01-01 → 2022-03-31
MCL Health-based Resolved 2022-01-01 → 2022-03-31
MCL Health-based Resolved 2022-01-01 → 2022-03-31
MCL Health-based Resolved 2022-01-01 → 2022-03-31
MCL Health-based Resolved 2017-07-01 → 2017-09-30
MCL Health-based Resolved 2017-07-01 → 2017-09-30
MCL Health-based Resolved 2017-07-01 → 2017-09-30
MCL Health-based Resolved 2017-07-01 → 2017-09-30
MCL Health-based Resolved 2017-07-01 → 2017-09-30
MCL Health-based Resolved 2017-07-01 → 2017-09-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
TTHM
114.45 µg/L 143%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 143 µg/L
132/132 SYR4 2012–2019
Chloroform
101 µg/L
No EPA limit set
worst single sample: 131 µg/L
131/131 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
61.32 µg/L 102%
of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 91.5 µg/L
130/130 SYR4 2012–2019
Bromodichloromethane
11.42 µg/L
No EPA limit set
worst single sample: 12.5 µg/L
129/129 SYR4 2012–2019
Trichloroacetic Acid
35.46 µg/L
No EPA limit set
worst single sample: 46 µg/L
128/129 SYR4 2012–2019
Dichloroacetic Acid
30.22 µg/L
No EPA limit set
worst single sample: 40.2 µg/L
127/127 SYR4 2012–2019
Dibromochloromethane
1.5 µg/L
No EPA limit set
worst single sample: 1.6 µg/L
71/128 SYR4 2012–2019
Monochloroacetic Acid
3.7805 µg/L
No EPA limit set
worst single sample: 5.7 µg/L
42/130 SYR4 2012–2019
Monobromoacetic Acid
9.55 µg/L
No EPA limit set
worst single sample: 12 µg/L
30/130 SYR4 2012–2019
Lead
0.0076 mg/L 51%
of the EPA limit 0.0150 mg/L
19/19 LCR 2024
Dibromoacetic Acid
1.75 µg/L
No EPA limit set
worst single sample: 2 µg/L
6/129 SYR4 2012–2019
Copper
86 µg/L 6.6%
of the EPA limit 1300 µg/L
worst single sample: 90 µg/L
5/5 SYR4 2018–2019
Lead
3.6 µg/L 24%
of the EPA limit 15 µg/L
worst single sample: 4 µg/L
5/5 SYR4 2018–2019
31 contaminants tested, none detected
11Cl-PF3OUdS4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaBromoformHfpo-DaNetfosaaNfdhaNmefosaaPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaLithium

Utility contact

Contact
BRADLEY, WILLIAM
Phone
518-209-2466

Frequently asked questions about Brunswick Consolidated Water District

Is Brunswick Consolidated Water District tap water safe to drink?

EPA monitoring detected 13 contaminants in Brunswick Consolidated Water District's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Brunswick Consolidated Water District's water?

EPA monitoring detected TTHM, Chloroform, Total Haloacetic Acids (HAA5), Bromodichloromethane, Trichloroacetic Acid, and others. The full list with the level and data source for each is above.

How many people does Brunswick Consolidated Water District serve?

Brunswick Consolidated Water District reports serving 7,050 people in New York, per its EPA record.

Has Brunswick Consolidated Water District had any water quality violations?

The EPA has 47 violations on file for Brunswick Consolidated Water District, of which 18 are health-based (a contaminant limit or required treatment was breached) and 5 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.