Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MR | Monitoring | Resolved | 1994-07-01 |
| MR | Monitoring | Archived | 1994-01-01 → 1994-06-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Chloroform | 30 µg/L No EPA limit set
worst single sample: 44 µg/L | 15/17 | SYR4 | 2012–2019 |
| cis-1,2-Dichloroethylene | 3.35 µg/L 4.8% of the EPA limit 70 µg/L
worst single sample: 3.7 µg/L | 15/39 | SYR4 | 2012–2019 |
| Bromodichloromethane | 17 µg/L No EPA limit set | 14/15 | SYR4 | 2012–2019 |
| Tetrachloroethylene | 3.24 µg/L 65% of the EPA limit 5 µg/L
worst single sample: 3.5 µg/L | 14/39 | SYR4 | 2012–2019 |
| Dibromochloromethane | 9.75 µg/L No EPA limit set
worst single sample: 12 µg/L | 11/13 | SYR4 | 2012–2019 |
| Trichloroethylene | 1.9 µg/L 38% of the EPA limit 5 µg/L
worst single sample: 2.1 µg/L | 11/39 | SYR4 | 2012–2019 |
| Nitrate | 870 µg/L 8.7% of the EPA limit 10000 µg/L | 8/8 | SYR4 | 2012–2015 |
| Dichloroacetic Acid | 11.48 µg/L No EPA limit set
worst single sample: 12 µg/L | 5/6 | SYR4 | 2012–2019 |
| Lead | 0.0079 mg/L 53% of the EPA limit 0.0150 mg/L | 5/5 | LCR | 2021 |
| Monochloroacetic Acid | 3.04 µg/L No EPA limit set
worst single sample: 3.3 µg/L | 5/6 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 7.04 µg/L No EPA limit set
worst single sample: 7.1 µg/L | 5/6 | SYR4 | 2012–2019 |
| Bromoform | 0.6355 µg/L No EPA limit set
worst single sample: 0.6400 µg/L | 4/6 | SYR4 | 2012–2019 |
| Dichloromethane | 5.93 µg/L 119% of the EPA limit, at the 95th percentile of samples — 5 µg/L
worst single sample: 6.8 µg/L | 4/37 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 1.74 µg/L No EPA limit set
worst single sample: 1.8 µg/L | 4/6 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 1 µg/L No EPA limit set | 4/6 | SYR4 | 2012–2019 |
| Antimony, Total | 0.4000 µg/L 6.7% of the EPA limit 6 µg/L | 3/3 | SYR4 | 2012–2018 |
| Barium | 117.9 µg/L 5.9% of the EPA limit 2000 µg/L
worst single sample: 120 µg/L | 3/3 | SYR4 | 2012–2018 |
| Beryllium, Total | 0.3000 µg/L 7.5% of the EPA limit 4 µg/L | 3/3 | SYR4 | 2012–2018 |
| Cadmium | 1 µg/L 20% of the EPA limit 5 µg/L | 3/3 | SYR4 | 2012–2018 |
| Chromium | 7 µg/L 7% of the EPA limit 100 µg/L | 3/3 | SYR4 | 2012–2018 |
| Selenium | 2 µg/L 4% of the EPA limit 50 µg/L | 3/3 | SYR4 | 2012–2018 |
| Thallium, Total | 0.3000 µg/L 15% of the EPA limit 2 µg/L | 3/3 | SYR4 | 2012–2018 |
| Arsenic | 1.4 µg/L 14% of the EPA limit 10 µg/L | 2/3 | SYR4 | 2012–2018 |
| Cyanide | 10 µg/L 5% of the EPA limit 200 µg/L | 2/2 | SYR4 | 2012–2015 |
| Fluoride | 500 µg/L 13% of the EPA limit 4000 µg/L | 2/2 | SYR4 | 2012–2015 |
| Mercury | 0.2000 µg/L 10% of the EPA limit 2 µg/L | 2/2 | SYR4 | 2012–2015 |
| TTHM | 37 µg/L 46% of the EPA limit 80 µg/L | 1/1 | SYR4 | 2014 |
| Total Haloacetic Acids (HAA5) | 19.6 µg/L 33% of the EPA limit 60 µg/L | 1/1 | SYR4 | 2014 |
16 contaminants tested, none detected
Utility contact
Frequently asked questions about Brewster Village
Is Brewster Village tap water safe to drink?
EPA monitoring detected 28 contaminants in Brewster Village's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Brewster Village's water?
EPA monitoring detected Chloroform, cis-1,2-Dichloroethylene, Bromodichloromethane, Tetrachloroethylene, Dibromochloromethane, and others. The full list with the level and data source for each is above.
How many people does Brewster Village serve?
Brewster Village reports serving 2,162 people in New York, per its EPA record.
Has Brewster Village had any water quality violations?
The EPA has 2 violations on file for Brewster Village, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.