← New York

Tap water quality report

Wallkill Consolidated Wd

EPA monitoring tested this supplier for 63 contaminants and detected 11. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

63
contaminants tested
11
detected
18,450
people served
95
health-based violations
Water source
Ground water under surface influence
Ownership
Local government
Counties served
Orange

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

95
health-based violations
470
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2022-01-01 → 2022-03-31
MCL Health-based Resolved 2022-01-01 → 2022-03-31
MCL Health-based Resolved 2022-01-01 → 2022-03-31
MCL Health-based Resolved 2022-01-01 → 2022-03-31
MCL Health-based Resolved 2022-01-01 → 2022-03-31
MCL Health-based Resolved 2021-10-01 → 2021-12-31
MCL Health-based Resolved 2021-10-01 → 2021-12-31
MCL Health-based Resolved 2021-10-01 → 2021-12-31
MCL Health-based Resolved 2021-10-01 → 2021-12-31
MCL Health-based Resolved 2021-10-01 → 2021-12-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
TTHM
104 µg/L 130%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 139 µg/L
133/133 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
52.04 µg/L 87%
of the EPA limit 60 µg/L
worst single sample: 71.4 µg/L
128/132 SYR4 2012–2019
Nitrate
1050 µg/L 11%
of the EPA limit 10000 µg/L
worst single sample: 1240 µg/L
50/50 SYR4 2012–2019
Barium
58.555 µg/L 2.9%
of the EPA limit 2000 µg/L
worst single sample: 77 µg/L
18/18 SYR4 2012–2019
Lead
0.0020 mg/L 13%
of the EPA limit 0.0150 mg/L
15/15 LCR 2023
Arsenic
1.2 µg/L 12%
of the EPA limit 10 µg/L
worst single sample: 1.3 µg/L
6/18 SYR4 2012–2019
Gross Alpha, Excl. Radon And U
1.829 pCi/L 12%
of the EPA limit 15 pCi/L
worst single sample: 1.9 pCi/L
2/4 SYR4 2012–2018
2,4-D
0.1000 µg/L 0.1%
of the EPA limit 70 µg/L
1/15 SYR4 2012–2019
Antimony, Total
0.6000 µg/L 10%
of the EPA limit 6 µg/L
1/18 SYR4 2012–2019
Chromium
9.1 µg/L 9.1%
of the EPA limit 100 µg/L
1/18 SYR4 2012–2019
Combined Uranium
0.5100 µg/L 1.7%
of the EPA limit 30 µg/L
1/6 SYR4 2012–2018
52 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-Dichloropropane2,4,5-TPAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneCombined Radium (-226 And -228)DichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebEthylene DibromideEndrinEthylbenzeneFluorideHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorOxamylPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
WALLKILL, SUPERVISOR & TOWN BD
Phone
845-692-7831
Email
[email protected]

Frequently asked questions about Wallkill Consolidated Wd

Is Wallkill Consolidated Wd tap water safe to drink?

EPA monitoring detected 11 contaminants in Wallkill Consolidated Wd's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Wallkill Consolidated Wd's water?

EPA monitoring detected TTHM, Total Haloacetic Acids (HAA5), Nitrate, Barium, Lead, and others. The full list with the level and data source for each is above.

How many people does Wallkill Consolidated Wd serve?

Wallkill Consolidated Wd reports serving 18,450 people in New York, per its EPA record.

Has Wallkill Consolidated Wd had any water quality violations?

The EPA has 470 violations on file for Wallkill Consolidated Wd, of which 95 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.