← New York

Tap water quality report

Ilion (V) Water Works

EPA monitoring tested this supplier for 108 contaminants and detected 20. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

108
contaminants tested
20
detected
8,053
people served
10
health-based violations
Water source
Surface water
Ownership
Local government
Counties served
Herkimer

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

10
health-based violations
78
violations on file
2
still open
ViolationTypeStatusPeriod
TT Health-based Addressed 2025-08-12
TT Health-based Addressed 2025-08-12
MCL Health-based Resolved 2003-01-01 → 2003-03-31
MCL Health-based Resolved 2003-01-01 → 2003-03-31
MCL Health-based Resolved 2003-01-01 → 2003-03-31
MCL Health-based Resolved 2003-01-01 → 2003-03-31
MCL Health-based Resolved 2002-10-01 → 2002-12-31
MCL Health-based Resolved 2002-10-01 → 2002-12-31
MCL Health-based Resolved 2002-10-01 → 2002-12-31
MCL Health-based Resolved 2002-10-01 → 2002-12-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
TTHM
92.24 µg/L 115%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 99 µg/L
57/57 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
42.8 µg/L 71%
of the EPA limit 60 µg/L
worst single sample: 52 µg/L
57/57 SYR4 2012–2019
Lead
0.0360 mg/L 240%
above the EPA limit of 0.0150 mg/L
16/16 LCR 2020
Nitrate
1200 µg/L 12%
of the EPA limit 10000 µg/L
16/40 SYR4 2012–2019
Barium
867.5 µg/L 43%
of the EPA limit 2000 µg/L
worst single sample: 900 µg/L
14/14 SYR4 2012–2019
Chromium
22.815 µg/L 23%
of the EPA limit 100 µg/L
worst single sample: 52 µg/L
14/14 SYR4 2012–2019
Fluoride
255 µg/L 6.4%
of the EPA limit 4000 µg/L
worst single sample: 310 µg/L
12/14 SYR4 2012–2019
Di(2-ethylhexyl) Phthalate
3.595 µg/L 60%
of the EPA limit 6 µg/L
worst single sample: 4.9 µg/L
10/28 SYR4 2012–2019
Bromodichloromethane
9.28 µg/L
No EPA limit set
worst single sample: 9.4 µg/L
7/7 SYR4 2012–2013
Chloroform
64.6 µg/L
No EPA limit set
worst single sample: 70 µg/L
7/7 SYR4 2012–2013
Dichloroacetic Acid
23.3 µg/L
No EPA limit set
worst single sample: 26 µg/L
7/7 SYR4 2012–2013
Trichloroacetic Acid
11.83 µg/L
No EPA limit set
worst single sample: 13 µg/L
7/7 SYR4 2012–2013
Dibromochloromethane
1.925 µg/L
No EPA limit set
worst single sample: 2 µg/L
4/7 SYR4 2012–2013
Copper
30.7 µg/L 2.4%
of the EPA limit 1300 µg/L
worst single sample: 31 µg/L
3/4 SYR4 2012–2016
Nitrate-Nitrite
1190 µg/L 12%
of the EPA limit 10000 µg/L
worst single sample: 1200 µg/L
3/4 SYR4 2012–2015
Lithium
61.2 µg/L
No EPA limit set
3/3 UCMR-5 2025
Selenium
1.19 µg/L 2.4%
of the EPA limit 50 µg/L
worst single sample: 1.2 µg/L
2/14 SYR4 2012–2019
Arsenic
1.1 µg/L 11%
of the EPA limit 10 µg/L
1/14 SYR4 2012–2019
Combined Radium (-226 And -228)
1.18 pCi/L 24%
of the EPA limit 5 pCi/L
1/5 SYR4 2015–2018
Combined Uranium
0.2480 µg/L 0.8%
of the EPA limit 30 µg/L
1/5 SYR4 2015–2018
88 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalAsbestosAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalBromoformChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneDichloromethaneDalaponDi(2-ethylhexyl) AdipateDibromoacetic AcidDinosebEthylene DibromideEndrinEthylbenzeneGross Alpha, Excl. Radon And UGross Beta Particle ActivityHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoLeadMercuryMethoxychlorMonobromoacetic AcidMonochloroacetic AcidNetfosaaNfdhaNmefosaaNitriteOxamylPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
ILION MAYOR AND VILLAGE BOARD
Phone
315-895-7449
Email
[email protected]

Frequently asked questions about Ilion (V) Water Works

Is Ilion (V) Water Works tap water safe to drink?

EPA monitoring detected 20 contaminants in Ilion (V) Water Works's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Ilion (V) Water Works's water?

EPA monitoring detected TTHM, Total Haloacetic Acids (HAA5), Lead, Nitrate, Barium, and others. The full list with the level and data source for each is above.

How many people does Ilion (V) Water Works serve?

Ilion (V) Water Works reports serving 8,053 people in New York, per its EPA record.

Has Ilion (V) Water Works had any water quality violations?

The EPA has 78 violations on file for Ilion (V) Water Works, of which 10 are health-based (a contaminant limit or required treatment was breached) and 2 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.