← New York

Tap water quality report

Gloversville (C) Water Works

EPA monitoring tested this supplier for 104 contaminants and detected 15. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

104
contaminants tested
15
detected
17,991
people served
4
health-based violations
Water source
Surface water
Ownership
Local government
Counties served
Fulton

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

4
health-based violations
205
violations on file
0
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 2002-01-01
TT Health-based Resolved 2002-01-01
TT Health-based Resolved 2001-11-01 → 2001-11-30
TT Health-based Resolved 2001-11-01 → 2001-11-30
MR Monitoring Resolved 2012-01-01 → 2012-12-31
MR Monitoring Resolved 2012-01-01 → 2012-12-31
MR Monitoring Resolved 2012-01-01 → 2012-12-31
MR Monitoring Resolved 2012-01-01 → 2012-12-31
MR Monitoring Resolved 2012-01-01 → 2012-12-31
MR Monitoring Resolved 2012-01-01 → 2012-12-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
TTHM
66.3 µg/L 83%
of the EPA limit 80 µg/L
worst single sample: 85.1 µg/L
128/128 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
41.74 µg/L 70%
of the EPA limit 60 µg/L
worst single sample: 62.5 µg/L
125/128 SYR4 2012–2019
Fluoride
1000 µg/L 25%
of the EPA limit 4000 µg/L
worst single sample: 1200 µg/L
86/86 SYR4 2012–2019
Chloroform
53.455 µg/L
No EPA limit set
worst single sample: 57.4 µg/L
28/28 SYR4 2012–2013
Dichloroacetic Acid
15.23 µg/L
No EPA limit set
worst single sample: 15.9 µg/L
28/28 SYR4 2012–2013
Trichloroacetic Acid
24.26 µg/L
No EPA limit set
worst single sample: 25.9 µg/L
28/28 SYR4 2012–2013
Bromodichloromethane
3.285 µg/L
No EPA limit set
worst single sample: 3.6 µg/L
24/28 SYR4 2012–2013
Lead
0.0079 mg/L 53%
of the EPA limit 0.0150 mg/L
13/13 LCR 2025
Monochloroacetic Acid
1.52 µg/L
No EPA limit set
worst single sample: 1.6 µg/L
9/28 SYR4 2012–2013
Barium
4.99 µg/L 0.2%
of the EPA limit 2000 µg/L
worst single sample: 5 µg/L
3/8 SYR4 2012–2019
Nitrate
30 µg/L 0.3%
of the EPA limit 10000 µg/L
2/16 SYR4 2012–2019
Copper
30 µg/L 2.3%
of the EPA limit 1300 µg/L
1/2 SYR4 2012–2013
Di(2-ethylhexyl) Phthalate
1.4 µg/L 23%
of the EPA limit 6 µg/L
1/10 SYR4 2013–2019
Nitrate-Nitrite
30 µg/L 0.3%
of the EPA limit 10000 µg/L
1/1 SYR4 2017
Lithium
9.02 µg/L
No EPA limit set
1/4 UCMR-5 2023
89 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalArsenicAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalBromoformChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumCombined Radium (-226 And -228)DichloromethaneDalaponDi(2-ethylhexyl) AdipateDibromoacetic AcidDibromochloromethaneDinosebEthylene DibromideEndrinEthylbenzeneHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoLeadMercuryMethoxychlorMonobromoacetic AcidNetfosaaNfdhaNmefosaaNitriteOxamylPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
GLOVERSVILLE CITY WATER COMMISSIONERS
Phone
518-773-4528
Email
[email protected]

Frequently asked questions about Gloversville (C) Water Works

Is Gloversville (C) Water Works tap water safe to drink?

EPA monitoring detected 15 contaminants in Gloversville (C) Water Works's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Gloversville (C) Water Works's water?

EPA monitoring detected TTHM, Total Haloacetic Acids (HAA5), Fluoride, Chloroform, Dichloroacetic Acid, and others. The full list with the level and data source for each is above.

How many people does Gloversville (C) Water Works serve?

Gloversville (C) Water Works reports serving 17,991 people in New York, per its EPA record.

Has Gloversville (C) Water Works had any water quality violations?

The EPA has 205 violations on file for Gloversville (C) Water Works, of which 4 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.