← New York

Tap water quality report

Adirondack Correctional Facility

EPA monitoring tested this supplier for 71 contaminants and detected 14. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

71
contaminants tested
14
detected
2,400
people served
4
health-based violations
Water source
Surface water
Ownership
State government
Counties served
Essex

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

4
health-based violations
89
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2019-04-01 → 2019-06-30
MCL Health-based Resolved 2019-04-01 → 2019-06-30
MCL Health-based Resolved 2019-04-01 → 2019-06-30
MCL Health-based Resolved 2019-04-01 → 2019-06-30
MR Monitoring Resolved 2017-01-01 → 2017-12-31
MR Monitoring Resolved 2017-01-01 → 2017-12-31
MR Monitoring Resolved 2017-01-01 → 2017-12-31
MR Monitoring Resolved 2017-01-01 → 2017-12-31
MR Monitoring Resolved 2017-01-01 → 2017-12-31
MR Monitoring Resolved 2017-01-01 → 2017-12-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Chloroform
84.1 µg/L
No EPA limit set
worst single sample: 95 µg/L
30/30 SYR4 2012–2019
Dichloroacetic Acid
30.2 µg/L
No EPA limit set
worst single sample: 39 µg/L
30/30 SYR4 2012–2019
TTHM
85.55 µg/L 107%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 97 µg/L
30/30 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
77.95 µg/L 130%
of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 129 µg/L
30/30 SYR4 2012–2019
Trichloroacetic Acid
51.05 µg/L
No EPA limit set
worst single sample: 90 µg/L
30/30 SYR4 2012–2019
Bromodichloromethane
1.8 µg/L
No EPA limit set
worst single sample: 1.9 µg/L
28/30 SYR4 2012–2019
Nitrate
400 µg/L 4%
of the EPA limit 10000 µg/L
16/16 SYR4 2012–2019
Lead
0.0039 mg/L 26%
of the EPA limit 0.0150 mg/L
12/12 LCR 2024
Barium
25.46 µg/L 1.3%
of the EPA limit 2000 µg/L
worst single sample: 31 µg/L
5/8 SYR4 2012–2019
Monochloroacetic Acid
1.67 µg/L
No EPA limit set
worst single sample: 1.7 µg/L
3/30 SYR4 2012–2019
Chromium
2.1 µg/L 2.1%
of the EPA limit 100 µg/L
1/8 SYR4 2012–2019
Combined Radium (-226 And -228)
0.1500 pCi/L 3%
of the EPA limit 5 pCi/L
1/1 SYR4 2014
Dalapon
1.19 µg/L 0.6%
of the EPA limit 200 µg/L
1/4 SYR4 2012–2018
Monobromoacetic Acid
1.6 µg/L
No EPA limit set
1/30 SYR4 2012–2019
57 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalArsenicAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalBromoformChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneDichloromethaneDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDibromoacetic AcidDibromochloromethaneDinosebEthylene DibromideEndrinEthylbenzeneFluorideGross Beta Particle ActivityHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorOxamylPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
ADIRONDACK CORRECTIONAL FACILIT - NYSDOC
Phone
518-891-1343

Frequently asked questions about Adirondack Correctional Facility

Is Adirondack Correctional Facility tap water safe to drink?

EPA monitoring detected 14 contaminants in Adirondack Correctional Facility's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Adirondack Correctional Facility's water?

EPA monitoring detected Chloroform, Dichloroacetic Acid, TTHM, Total Haloacetic Acids (HAA5), Trichloroacetic Acid, and others. The full list with the level and data source for each is above.

How many people does Adirondack Correctional Facility serve?

Adirondack Correctional Facility reports serving 2,400 people in New York, per its EPA record.

Has Adirondack Correctional Facility had any water quality violations?

The EPA has 89 violations on file for Adirondack Correctional Facility, of which 4 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.