← New York

Tap water quality report

Springville Village

EPA monitoring tested this supplier for 102 contaminants and detected 17. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

102
contaminants tested
17
detected
4,266
people served
0
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Erie

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

0
health-based violations
267
violations on file
0
still open
ViolationTypeStatusPeriod
MR Monitoring Resolved 2018-01-01 → 2018-12-31
MR Monitoring Resolved 2018-01-01 → 2018-12-31
MR Monitoring Resolved 2018-01-01 → 2018-12-31
MR Monitoring Resolved 2017-01-01 → 2018-06-30
MR Monitoring Resolved 2017-01-01 → 2018-06-30
MR Monitoring Resolved 2017-01-01 → 2018-06-30
MR Monitoring Resolved 2017-01-01 → 2018-06-30
MR Monitoring Resolved 2017-01-01 → 2018-06-30
MR Monitoring Resolved 2017-01-01 → 2018-06-30
MR Monitoring Resolved 2017-01-01 → 2018-06-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Lead
0.0020 mg/L 13%
of the EPA limit 0.0150 mg/L
10/10 LCR 2025
Bromodichloromethane
12.6125 µg/L
No EPA limit set
worst single sample: 14.1 µg/L
6/6 SYR4 2014–2019
Bromoform
2.07 µg/L
No EPA limit set
worst single sample: 2.21 µg/L
6/6 SYR4 2014–2019
Chloroform
18.875 µg/L
No EPA limit set
worst single sample: 21.8 µg/L
6/6 SYR4 2014–2019
Dibromochloromethane
7.2575 µg/L
No EPA limit set
worst single sample: 7.82 µg/L
6/6 SYR4 2014–2019
Dichloroacetic Acid
8.345 µg/L
No EPA limit set
worst single sample: 9.95 µg/L
6/6 SYR4 2014–2019
TTHM
40.35 µg/L 50%
of the EPA limit 80 µg/L
worst single sample: 45.4 µg/L
6/6 SYR4 2014–2019
Total Haloacetic Acids (HAA5)
15.96 µg/L 27%
of the EPA limit 60 µg/L
worst single sample: 18.02 µg/L
6/6 SYR4 2014–2019
Trichloroacetic Acid
3.405 µg/L
No EPA limit set
worst single sample: 3.48 µg/L
6/6 SYR4 2014–2019
Dibromoacetic Acid
3.002 µg/L
No EPA limit set
worst single sample: 3.07 µg/L
5/6 SYR4 2014–2019
Fluoride
1044 µg/L 26%
of the EPA limit 4000 µg/L
worst single sample: 1050 µg/L
3/3 SYR4 2012–2019
Monochloroacetic Acid
2.17 µg/L
No EPA limit set
worst single sample: 2.3 µg/L
3/6 SYR4 2014–2019
Barium
911.855 µg/L 46%
of the EPA limit 2000 µg/L
worst single sample: 955 µg/L
2/3 SYR4 2012–2019
Monobromoacetic Acid
0.6790 µg/L
No EPA limit set
worst single sample: 0.6800 µg/L
2/6 SYR4 2014–2019
Nitrate
67 µg/L 0.7%
of the EPA limit 10000 µg/L
2/18 SYR4 2012–2019
Antimony, Total
0.8100 µg/L 14%
of the EPA limit 6 µg/L
1/3 SYR4 2012–2019
Lithium
9.16 µg/L
No EPA limit set
1/2 UCMR-5 2025
85 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaArsenicAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumCombined Radium (-226 And -228)Combined UraniumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebEthylene DibromideEndrinEthylbenzeneGross Alpha, Excl. Radon And UHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNetfosaaNfdhaNmefosaaOxamylPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
DOMES, TIMOTHY

Frequently asked questions about Springville Village

Is Springville Village tap water safe to drink?

EPA monitoring detected 17 contaminants in Springville Village's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Springville Village's water?

EPA monitoring detected Lead, Bromodichloromethane, Bromoform, Chloroform, Dibromochloromethane, and others. The full list with the level and data source for each is above.

How many people does Springville Village serve?

Springville Village reports serving 4,266 people in New York, per its EPA record.

Has Springville Village had any water quality violations?

The EPA has 267 violations on file for Springville Village, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.