← New York

Tap water quality report

Pinebrook Estates

EPA monitoring tested this supplier for 50 contaminants and detected 18. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

50
contaminants tested
18
detected
400
people served
2
health-based violations
Water source
SWP
Ownership
Private
Counties served
Dutchess

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

2
health-based violations
34
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2009-10-01 → 2009-10-31
MCL Health-based Resolved 2009-10-01 → 2009-10-31
MR Monitoring Resolved 2025-10-01
MR Monitoring Resolved 2025-10-01
MON Monitoring Resolved 2019-07-01 → 2019-07-31
MON Monitoring Resolved 2019-07-01 → 2019-07-31
Other Monitoring Resolved 2009-09-02
Other Monitoring Resolved 2009-09-02
Other Monitoring Resolved 2008-09-02
Other Monitoring Resolved 2008-09-02

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Lead
0.00060 mg/L 4%
of the EPA limit 0.0150 mg/L
20/20 LCR 2025
Nitrate
2690 µg/L 27%
of the EPA limit 10000 µg/L
16/18 SYR4 2012–2019
Barium
243.45 µg/L 12%
of the EPA limit 2000 µg/L
worst single sample: 264 µg/L
4/4 SYR4 2013–2019
Bromodichloromethane
31.345 µg/L
No EPA limit set
worst single sample: 33.4 µg/L
4/4 SYR4 2012–2018
Chloroform
42.46 µg/L
No EPA limit set
worst single sample: 44.5 µg/L
4/4 SYR4 2012–2018
Combined Radium (-226 And -228)
5.166 pCi/L 103%
of the EPA limit, at the 95th percentile of samples — 5 pCi/L
worst single sample: 5.28 pCi/L
4/7 SYR4 2013–2019
Dibromochloromethane
10.685 µg/L
No EPA limit set
worst single sample: 10.7 µg/L
4/4 SYR4 2012–2018
Dichloroacetic Acid
17.16 µg/L
No EPA limit set
worst single sample: 18 µg/L
4/4 SYR4 2012–2018
TTHM
83.73 µg/L 105%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 88.5 µg/L
4/4 SYR4 2012–2018
Total Haloacetic Acids (HAA5)
33.905 µg/L 57%
of the EPA limit 60 µg/L
worst single sample: 35 µg/L
4/4 SYR4 2012–2018
Trichloroacetic Acid
16.4 µg/L
No EPA limit set
worst single sample: 17 µg/L
4/4 SYR4 2012–2018
Combined Uranium
1.099 µg/L 3.7%
of the EPA limit 30 µg/L
worst single sample: 1.1 µg/L
3/4 SYR4 2013–2019
Arsenic
0.5000 µg/L 5%
of the EPA limit 10 µg/L
2/5 SYR4 2013–2019
Bromoform
0.8400 µg/L
No EPA limit set
1/4 SYR4 2012–2018
Copper
429 µg/L 33%
of the EPA limit 1300 µg/L
1/1 SYR4 2017
Dibromoacetic Acid
2.4 µg/L
No EPA limit set
1/4 SYR4 2012–2018
Fluoride
31.5 µg/L 0.8%
of the EPA limit 4000 µg/L
1/4 SYR4 2013–2019
Gross Alpha, Excl. Radon And U
3 pCi/L 20%
of the EPA limit 15 pCi/L
1/3 SYR4 2013–2019
32 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-DichloropropaneAntimony, TotalBenzeneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbon TetrachlorideChromiumDichloromethaneEthylbenzeneGross Beta Particle ActivityLeadMercuryMonobromoacetic AcidMonochloroacetic AcidSeleniumStyreneTetrachloroethyleneThallium, TotalTolueneTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
CHURINS, JONATHAN
Phone
845-486-3624
Email
[email protected]

Frequently asked questions about Pinebrook Estates

Is Pinebrook Estates tap water safe to drink?

EPA monitoring detected 18 contaminants in Pinebrook Estates's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Pinebrook Estates's water?

EPA monitoring detected Lead, Nitrate, Barium, Bromodichloromethane, Chloroform, and others. The full list with the level and data source for each is above.

How many people does Pinebrook Estates serve?

Pinebrook Estates reports serving 400 people in New York, per its EPA record.

Has Pinebrook Estates had any water quality violations?

The EPA has 34 violations on file for Pinebrook Estates, of which 2 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.