Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2011-10-01 → 2011-12-31 |
| MCL | Health-based | Resolved | 2011-10-01 → 2011-12-31 |
| MCL | Health-based | Resolved | 2011-07-01 → 2011-09-30 |
| MCL | Health-based | Resolved | 2011-07-01 → 2011-09-30 |
| MCL | Health-based | Resolved | 2011-07-01 → 2011-09-30 |
| MCL | Health-based | Resolved | 2011-07-01 → 2011-09-30 |
| MCL | Health-based | Resolved | 2011-04-01 → 2011-06-30 |
| MCL | Health-based | Resolved | 2011-04-01 → 2011-06-30 |
| MCL | Health-based | Resolved | 2011-04-01 → 2011-06-30 |
| MCL | Health-based | Resolved | 2011-04-01 → 2011-06-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Chloroform | 114 µg/L No EPA limit set
worst single sample: 130 µg/L | 17/17 | SYR4 | 2012–2018 |
| TTHM | 120.2 µg/L 150% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 137 µg/L | 17/17 | SYR4 | 2012–2018 |
| Bromodichloromethane | 8.15 µg/L No EPA limit set
worst single sample: 8.9 µg/L | 16/16 | SYR4 | 2012–2018 |
| Total Haloacetic Acids (HAA5) | 101.25 µg/L 169% of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 147 µg/L | 16/16 | SYR4 | 2012–2018 |
| Dichloroacetic Acid | 36.4 µg/L No EPA limit set
worst single sample: 49 µg/L | 15/16 | SYR4 | 2012–2018 |
| Trichloroacetic Acid | 66.7 µg/L No EPA limit set
worst single sample: 94 µg/L | 15/16 | SYR4 | 2012–2018 |
| Nitrate | 190 µg/L 1.9% of the EPA limit 10000 µg/L | 12/12 | SYR4 | 2012–2016 |
| Lead | 0.0010 mg/L 6.7% of the EPA limit 0.0150 mg/L | 9/9 | LCR | 2025 |
| Dibromochloromethane | 1.35 µg/L No EPA limit set
worst single sample: 1.4 µg/L | 6/16 | SYR4 | 2012–2018 |
| Barium | 14.55 µg/L 0.7% of the EPA limit 2000 µg/L
worst single sample: 15 µg/L | 4/4 | SYR4 | 2012–2015 |
| Nitrate-Nitrite | 175 µg/L 1.8% of the EPA limit 10000 µg/L
worst single sample: 190 µg/L | 4/4 | SYR4 | 2012–2015 |
| Copper | 22.45 µg/L 1.7% of the EPA limit 1300 µg/L
worst single sample: 23 µg/L | 2/2 | SYR4 | 2013–2014 |
| Dalapon | 1.8 µg/L 0.9% of the EPA limit 200 µg/L | 1/2 | SYR4 | 2012–2015 |
| Hexachlorocyclopentadiene | 0.1200 µg/L 0.2% of the EPA limit 50 µg/L | 1/3 | SYR4 | 2012–2015 |
| Monochloroacetic Acid | 4.2 µg/L No EPA limit set | 1/16 | SYR4 | 2012–2018 |
65 contaminants tested, none detected
Utility contact
Frequently asked questions about Olivet Management, Llc
Is Olivet Management, Llc tap water safe to drink?
EPA monitoring detected 15 contaminants in Olivet Management, Llc's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Olivet Management, Llc's water?
EPA monitoring detected Chloroform, TTHM, Bromodichloromethane, Total Haloacetic Acids (HAA5), Dichloroacetic Acid, and others. The full list with the level and data source for each is above.
How many people does Olivet Management, Llc serve?
Olivet Management, Llc reports serving 79 people in New York, per its EPA record.
Has Olivet Management, Llc had any water quality violations?
The EPA has 55 violations on file for Olivet Management, Llc, of which 14 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.