← New York

Tap water quality report

Poughkeepsie Townwide Wd

EPA monitoring tested this supplier for 43 contaminants and detected 12. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

43
contaminants tested
12
detected
43,000
people served
0
health-based violations
Water source
SWP
Ownership
Local government
Counties served
Dutchess

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

0
health-based violations
6
violations on file
0
still open
ViolationTypeStatusPeriod
MR Monitoring Resolved 2007-06-01
MR Monitoring Resolved 2007-06-01
MR Monitoring Resolved 2002-10-01 → 2002-12-31
MR Monitoring Resolved 2002-10-01 → 2002-12-31
MR Monitoring Resolved 2002-10-01 → 2002-12-31
MR Monitoring Resolved 2002-10-01 → 2002-12-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Total Haloacetic Acids (HAA5)
54.9 µg/L 91%
of the EPA limit 60 µg/L
worst single sample: 70 µg/L
123/124 SYR4 2012–2019
Trichloroacetic Acid
34.9 µg/L
No EPA limit set
worst single sample: 44 µg/L
123/124 SYR4 2012–2019
Dichloroacetic Acid
23.95 µg/L
No EPA limit set
worst single sample: 34 µg/L
122/124 SYR4 2012–2019
Chloroform
96.3 µg/L
No EPA limit set
worst single sample: 107 µg/L
116/116 SYR4 2012–2019
TTHM
125.025 µg/L 156%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 147 µg/L
116/116 SYR4 2012–2019
Bromodichloromethane
31.86 µg/L
No EPA limit set
worst single sample: 36.9 µg/L
115/116 SYR4 2012–2019
Dibromochloromethane
18.24 µg/L
No EPA limit set
worst single sample: 39.4 µg/L
105/116 SYR4 2012–2019
Dibromoacetic Acid
7.15 µg/L
No EPA limit set
worst single sample: 14 µg/L
51/124 SYR4 2012–2019
Monobromoacetic Acid
14 µg/L
No EPA limit set
worst single sample: 19 µg/L
23/124 SYR4 2012–2019
Monochloroacetic Acid
18.2 µg/L
No EPA limit set
worst single sample: 19 µg/L
17/124 SYR4 2012–2019
Lead
0.0042 mg/L 28%
of the EPA limit 0.0150 mg/L
16/16 LCR 2023
Bromoform
13.58 µg/L
No EPA limit set
worst single sample: 18.2 µg/L
15/116 SYR4 2012–2019
31 contaminants tested, none detected
11Cl-PF3OUdS4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaBromateHfpo-DaNetfosaaNfdhaNmefosaaPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaLithium

Utility contact

Contact
TOWN OF POUGHKEEPSIE
Phone
845-485-3603
Email
[email protected]

Frequently asked questions about Poughkeepsie Townwide Wd

Is Poughkeepsie Townwide Wd tap water safe to drink?

EPA monitoring detected 12 contaminants in Poughkeepsie Townwide Wd's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Poughkeepsie Townwide Wd's water?

EPA monitoring detected Total Haloacetic Acids (HAA5), Trichloroacetic Acid, Dichloroacetic Acid, Chloroform, TTHM, and others. The full list with the level and data source for each is above.

How many people does Poughkeepsie Townwide Wd serve?

Poughkeepsie Townwide Wd reports serving 43,000 people in New York, per its EPA record.

Has Poughkeepsie Townwide Wd had any water quality violations?

The EPA has 6 violations on file for Poughkeepsie Townwide Wd, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.