← New York

Tap water quality report

Mountain View Mobile Home Park - Fenton

EPA monitoring tested this supplier for 45 contaminants and detected 17. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

45
contaminants tested
17
detected
122
people served
20
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Broome

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

20
health-based violations
169
violations on file
4
still open
ViolationTypeStatusPeriod
TT Health-based Unaddressed 2024-10-17
TT Health-based Unaddressed 2024-10-17
MCL Health-based Resolved 2008-07-01 → 2008-09-30
MCL Health-based Resolved 2008-07-01 → 2008-09-30
MCL Health-based Resolved 2008-07-01 → 2008-09-30
MCL Health-based Resolved 2008-07-01 → 2008-09-30
MCL Health-based Resolved 2007-07-01 → 2007-09-30
MCL Health-based Resolved 2007-07-01 → 2007-09-30
MCL Health-based Resolved 2007-07-01 → 2007-09-30
MCL Health-based Resolved 2007-07-01 → 2007-09-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate
319 µg/L 3.2%
of the EPA limit 10000 µg/L
8/14 SYR4 2012–2019
Bromoform
26.38 µg/L
No EPA limit set
worst single sample: 27.3 µg/L
3/3 SYR4 2013–2019
Dibromoacetic Acid
16.729 µg/L
No EPA limit set
worst single sample: 17.5 µg/L
3/3 SYR4 2013–2019
Dibromochloromethane
9.853 µg/L
No EPA limit set
worst single sample: 10.7 µg/L
3/3 SYR4 2013–2019
Lead
0.0042 mg/L 28%
of the EPA limit 0.0150 mg/L
3/3 LCR 2024
TTHM
58.45 µg/L 73%
of the EPA limit 80 µg/L
worst single sample: 61.6 µg/L
3/3 SYR4 2013–2019
Total Haloacetic Acids (HAA5)
90.46 µg/L 151%
of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 99 µg/L
3/3 SYR4 2013–2019
Barium
1358.55 µg/L 68%
of the EPA limit 2000 µg/L
worst single sample: 1400 µg/L
2/2 SYR4 2014–2017
Bromodichloromethane
11.0465 µg/L
No EPA limit set
worst single sample: 11.6 µg/L
2/3 SYR4 2013–2019
Dichloroacetic Acid
34.26 µg/L
No EPA limit set
worst single sample: 36 µg/L
2/3 SYR4 2013–2019
Fluoride
139 µg/L 3.5%
of the EPA limit 4000 µg/L
worst single sample: 140 µg/L
2/2 SYR4 2014–2017
Arsenic
1.1 µg/L 11%
of the EPA limit 10 µg/L
1/2 SYR4 2014–2017
Chloroform
34.4 µg/L
No EPA limit set
1/3 SYR4 2013–2019
Combined Radium (-226 And -228)
1.064 pCi/L 21%
of the EPA limit 5 pCi/L
1/1 SYR4 2016
Monobromoacetic Acid
1.4 µg/L
No EPA limit set
1/3 SYR4 2013–2019
Monochloroacetic Acid
2.6 µg/L
No EPA limit set
1/3 SYR4 2013–2019
Trichloroacetic Acid
45.2 µg/L
No EPA limit set
1/3 SYR4 2013–2019
28 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-DichloropropaneAntimony, TotalBenzeneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbon TetrachlorideChromiumDichloromethaneEthylbenzeneMercurySeleniumStyreneTetrachloroethyleneThallium, TotalTolueneTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
REYNOLDS, JACOB (JAKE) W.
Email
[email protected]

Frequently asked questions about Mountain View Mobile Home Park - Fenton

Is Mountain View Mobile Home Park - Fenton tap water safe to drink?

EPA monitoring detected 17 contaminants in Mountain View Mobile Home Park - Fenton's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Mountain View Mobile Home Park - Fenton's water?

EPA monitoring detected Nitrate, Bromoform, Dibromoacetic Acid, Dibromochloromethane, Lead, and others. The full list with the level and data source for each is above.

How many people does Mountain View Mobile Home Park - Fenton serve?

Mountain View Mobile Home Park - Fenton reports serving 122 people in New York, per its EPA record.

Has Mountain View Mobile Home Park - Fenton had any water quality violations?

The EPA has 169 violations on file for Mountain View Mobile Home Park - Fenton, of which 20 are health-based (a contaminant limit or required treatment was breached) and 4 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.