Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2023-01-01 |
| TT | Health-based | Resolved | 2023-01-01 |
| TT | Health-based | Resolved | 2023-01-01 |
| MCL | Health-based | Resolved | 2016-04-01 → 2016-06-30 |
| MCL | Health-based | Resolved | 2016-04-01 → 2016-06-30 |
| MCL | Health-based | Resolved | 2016-04-01 → 2016-06-30 |
| MCL | Health-based | Resolved | 2002-10-01 → 2002-12-31 |
| MCL | Health-based | Resolved | 2002-10-01 → 2002-12-31 |
| MCL | Health-based | Resolved | 2002-10-01 → 2002-12-31 |
| TT | Health-based | Resolved | 1994-01-01 → 1994-01-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Bromodichloromethane | 16.16 µg/L No EPA limit set
worst single sample: 17.6 µg/L | 50/50 | SYR4 | 2013–2019 |
| Dichloroacetic Acid | 17.7 µg/L No EPA limit set
worst single sample: 22 µg/L | 50/50 | SYR4 | 2013–2019 |
| Total Haloacetic Acids (HAA5) | 68.115 µg/L 114% of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 92.6 µg/L | 50/50 | SYR4 | 2013–2019 |
| Chloroform | 98.4 µg/L No EPA limit set
worst single sample: 127 µg/L | 49/49 | SYR4 | 2013–2019 |
| TTHM | 113.94 µg/L 142% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 137 µg/L | 49/49 | SYR4 | 2013–2019 |
| Trichloroacetic Acid | 49.7 µg/L No EPA limit set
worst single sample: 73.9 µg/L | 47/50 | SYR4 | 2013–2019 |
| Dibromochloromethane | 2.8725 µg/L No EPA limit set
worst single sample: 3.2 µg/L | 32/50 | SYR4 | 2013–2019 |
| Monobromoacetic Acid | 1.185 µg/L No EPA limit set
worst single sample: 1.32 µg/L | 19/50 | SYR4 | 2013–2019 |
| Monochloroacetic Acid | 2.63 µg/L No EPA limit set
worst single sample: 2.9 µg/L | 19/50 | SYR4 | 2013–2019 |
| Lead | 0.0020 mg/L 13% of the EPA limit 0.0150 mg/L | 10/10 | LCR | 2023 |
| Barium | 30.5 µg/L 1.5% of the EPA limit 2000 µg/L
worst single sample: 32 µg/L | 6/6 | SYR4 | 2013–2019 |
| Arsenic | 0.9000 µg/L 9% of the EPA limit 10 µg/L | 1/6 | SYR4 | 2013–2019 |
| Chromium | 3 µg/L 3% of the EPA limit 100 µg/L | 1/6 | SYR4 | 2013–2019 |
| Combined Radium (-226 And -228) | 0.9700 pCi/L 19% of the EPA limit 5 pCi/L | 1/1 | SYR4 | 2015 |
| Dalapon | 1.26 µg/L 0.6% of the EPA limit 200 µg/L | 1/6 | SYR4 | 2013–2019 |
86 contaminants tested, none detected
Frequently asked questions about Watervliet City
Is Watervliet City tap water safe to drink?
EPA monitoring detected 15 contaminants in Watervliet City's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Watervliet City's water?
EPA monitoring detected Bromodichloromethane, Dichloroacetic Acid, Total Haloacetic Acids (HAA5), Chloroform, TTHM, and others. The full list with the level and data source for each is above.
How many people does Watervliet City serve?
Watervliet City reports serving 9,889 people, per its EPA record.
Has Watervliet City had any water quality violations?
The EPA has 31 violations on file for Watervliet City, of which 11 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.