← New York

Tap water quality report

Voorheesville Village

EPA monitoring tested this supplier for 102 contaminants and detected 20. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

102
contaminants tested
20
detected
3,100
people served
2
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Albany

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

2
health-based violations
208
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 1997-09-01 → 1997-09-30
MCL Health-based Resolved 1997-09-01 → 1997-09-30
MON Monitoring Resolved 2024-11-01 → 2024-11-30
MON Monitoring Resolved 2024-11-01 → 2024-11-30
MON Monitoring Resolved 2024-11-01 → 2024-11-30
MON Monitoring Resolved 2024-10-01 → 2024-10-31
MON Monitoring Resolved 2024-10-01 → 2024-10-31
MON Monitoring Resolved 2024-10-01 → 2024-10-31
MR Monitoring Archived 2024-10-01 → 2024-12-31
MR Monitoring Archived 2024-10-01 → 2024-12-31

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
Pfhxa 0.0076 µg/L 3/4 2024
Pfpea 0.0102 µg/L 3/4 2024
PFOA 0.0041 µg/L 1/4 2024

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate
6105 µg/L 61%
of the EPA limit 10000 µg/L
worst single sample: 6300 µg/L
24/24 SYR4 2013–2019
Lead
0.0060 mg/L 40%
of the EPA limit 0.0150 mg/L
10/10 LCR 2022
Barium
55.95 µg/L 2.8%
of the EPA limit 2000 µg/L
worst single sample: 57 µg/L
4/4 SYR4 2015–2018
Lithium
9.78 µg/L
No EPA limit set
3/4 UCMR-5 2024
Bromodichloromethane
6.415 µg/L
No EPA limit set
worst single sample: 6.5 µg/L
2/2 SYR4 2013–2016
Bromoform
2.195 µg/L
No EPA limit set
worst single sample: 2.2 µg/L
2/2 SYR4 2013–2016
Chloroform
18.07 µg/L
No EPA limit set
worst single sample: 18.9 µg/L
2/2 SYR4 2013–2016
Combined Radium (-226 And -228)
0.7062 pCi/L 14%
of the EPA limit 5 pCi/L
worst single sample: 0.7160 pCi/L
2/2 SYR4 2017
Combined Uranium
0.2858 µg/L 1%
of the EPA limit 30 µg/L
worst single sample: 0.2860 µg/L
2/2 SYR4 2017
Dibromochloromethane
4.755 µg/L
No EPA limit set
worst single sample: 4.8 µg/L
2/2 SYR4 2013–2016
Gross Alpha, Excl. Radon And U
1.524 pCi/L 10%
of the EPA limit 15 pCi/L
worst single sample: 1.59 pCi/L
2/2 SYR4 2017
TTHM
31.345 µg/L 39%
of the EPA limit 80 µg/L
worst single sample: 32.3 µg/L
2/2 SYR4 2013–2016
Total Haloacetic Acids (HAA5)
4.8 µg/L 8%
of the EPA limit 60 µg/L
worst single sample: 5 µg/L
2/2 SYR4 2013–2016
Antimony, Total
2.9 µg/L 48%
of the EPA limit 6 µg/L
1/3 SYR4 2015–2018
Dichloroacetic Acid
1 µg/L
No EPA limit set
1/2 SYR4 2013–2016
Monochloroacetic Acid
5 µg/L
No EPA limit set
1/2 SYR4 2013–2016
Selenium
2 µg/L 4%
of the EPA limit 50 µg/L
1/3 SYR4 2015–2018
82 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaArsenicAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDibromoacetic AcidDinosebEthylene DibromideEndrinEthylbenzeneFluorideHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidNetfosaaNfdhaNmefosaaOxamylPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPFHXSPfmbaPfmpaPFNAPFOSPfpesPftaPftrdaPfunaPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroacetic AcidTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
HOTALING, BRETT
Phone
518-765-4512
Email
[email protected]

Frequently asked questions about Voorheesville Village

Is Voorheesville Village tap water safe to drink?

EPA monitoring detected 20 contaminants in Voorheesville Village's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Voorheesville Village's water?

EPA monitoring detected Nitrate, Lead, Barium, Pfhxa, Pfpea, and others. The full list with the level and data source for each is above.

How many people does Voorheesville Village serve?

Voorheesville Village reports serving 3,100 people in New York, per its EPA record.

Has Voorheesville Village had any water quality violations?

The EPA has 208 violations on file for Voorheesville Village, of which 2 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.