Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MR | Monitoring | Resolved | 2020-01-01 → 2020-12-31 |
| MR | Monitoring | Resolved | 2020-01-01 → 2020-12-31 |
| MR | Monitoring | Resolved | 2020-01-01 → 2020-12-31 |
| MR | Monitoring | Resolved | 2020-01-01 → 2020-12-31 |
| MR | Monitoring | Resolved | 2020-01-01 → 2020-12-31 |
| MR | Monitoring | Resolved | 2020-01-01 → 2020-12-31 |
| Other | Monitoring | Archived | 1987-12-31 → 1988-01-30 |
| Other | Monitoring | Archived | 1987-11-30 → 1987-12-29 |
| Other | Monitoring | Archived | 1981-12-31 → 1982-01-30 |
| Other | Monitoring | Archived | 1981-01-31 → 1981-02-28 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 3760 µg/L 38% of the EPA limit 10000 µg/L
worst single sample: 3800 µg/L | 56/56 | SYR4 | 2012–2019 |
| Arsenic | 11 µg/L 110% of the EPA limit, at the 95th percentile of samples — 10 µg/L
worst single sample: 12 µg/L | 44/57 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 3700 µg/L 37% of the EPA limit 10000 µg/L
worst single sample: 3760 µg/L | 21/21 | SYR4 | 2013–2019 |
| Combined Uranium | 7.675 µg/L 26% of the EPA limit 30 µg/L
worst single sample: 8 µg/L | 14/14 | SYR4 | 2013–2019 |
| Fluoride | 1100 µg/L 28% of the EPA limit 4000 µg/L | 14/14 | SYR4 | 2013–2019 |
| Lead | 0.00080 mg/L 5.3% of the EPA limit 0.0150 mg/L | 14/14 | LCR | 2023 |
| Selenium | 16.26 µg/L 33% of the EPA limit 50 µg/L
worst single sample: 18.6 µg/L | 14/15 | SYR4 | 2013–2019 |
| Chromium | 44.5 µg/L 45% of the EPA limit 100 µg/L
worst single sample: 45 µg/L | 11/14 | SYR4 | 2013–2019 |
| Bromodichloromethane | 1.7 µg/L No EPA limit set | 8/8 | SYR4 | 2012–2019 |
| Bromoform | 7.775 µg/L No EPA limit set
worst single sample: 9 µg/L | 8/8 | SYR4 | 2012–2019 |
| Dibromochloromethane | 4.395 µg/L No EPA limit set
worst single sample: 4.5 µg/L | 8/8 | SYR4 | 2012–2019 |
| TTHM | 13.695 µg/L 17% of the EPA limit 80 µg/L
worst single sample: 14.5 µg/L | 8/8 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 2.7 µg/L No EPA limit set
worst single sample: 2.8 µg/L | 5/7 | SYR4 | 2012–2019 |
| Gross Alpha, Excl. Radon And U | 6.8 pCi/L 45% of the EPA limit 15 pCi/L
worst single sample: 7 pCi/L | 5/7 | SYR4 | 2013–2014 |
| Total Haloacetic Acids (HAA5) | 2.7 µg/L 4.5% of the EPA limit 60 µg/L
worst single sample: 2.8 µg/L | 5/7 | SYR4 | 2012–2019 |
| Chloroform | 4.17 µg/L No EPA limit set
worst single sample: 4.8 µg/L | 4/10 | SYR4 | 2012–2019 |
| Barium | 44.84 µg/L 2.2% of the EPA limit 2000 µg/L
worst single sample: 44.9 µg/L | 3/14 | SYR4 | 2013–2019 |
| Copper | 22.3 µg/L 1.7% of the EPA limit 1300 µg/L
worst single sample: 23 µg/L | 3/14 | SYR4 | 2013–2019 |
| Lead | 0.9700 µg/L 6.5% of the EPA limit 15 µg/L
worst single sample: 1 µg/L | 2/14 | SYR4 | 2013–2019 |
| Mercury | 0.3560 µg/L 18% of the EPA limit 2 µg/L | 1/14 | SYR4 | 2013–2019 |
| Xylenes, Total | 0.5600 µg/L 0% of the EPA limit 10000 µg/L | 1/27 | SYR4 | 2013–2019 |
61 contaminants tested, none detected
Utility contact
Frequently asked questions about Searchlight Water Company
Is Searchlight Water Company tap water safe to drink?
EPA monitoring detected 21 contaminants in Searchlight Water Company's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Searchlight Water Company's water?
EPA monitoring detected Nitrate, Arsenic, Nitrate-Nitrite, Combined Uranium, Fluoride, and others. The full list with the level and data source for each is above.
How many people does Searchlight Water Company serve?
Searchlight Water Company reports serving 760 people in Nevada, per its EPA record.
Has Searchlight Water Company had any water quality violations?
The EPA has 12 violations on file for Searchlight Water Company, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.