← Nevada

Tap water quality report

Luna Vista

EPA monitoring tested this supplier for 46 contaminants and detected 10. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

46
contaminants tested
10
detected
66
people served
20
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Clark

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

20
health-based violations
175
violations on file
0
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 2024-10-17
TT Health-based Resolved 2024-10-17
TT Health-based Resolved 2024-10-17
MCL Health-based Resolved 2018-04-01 → 2018-06-30
MCL Health-based Resolved 2018-04-01 → 2018-06-30
MCL Health-based Resolved 2018-04-01 → 2018-06-30
MCL Health-based Resolved 2018-04-01 → 2018-06-30
MCL Health-based Resolved 2018-01-01 → 2018-03-31
MCL Health-based Resolved 2018-01-01 → 2018-03-31
MCL Health-based Resolved 2018-01-01 → 2018-03-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate
2000 µg/L 20%
of the EPA limit 10000 µg/L
16/16 SYR4 2012–2019
Arsenic
15.31 µg/L 153%
of the EPA limit, at the 95th percentile of samples — 10 µg/L
worst single sample: 21.8 µg/L
12/13 SYR4 2014–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
12/12 LCR 2025
Fluoride
800 µg/L 20%
of the EPA limit 4000 µg/L
3/3 SYR4 2014–2018
Nitrate-Nitrite
1940 µg/L 19%
of the EPA limit 10000 µg/L
worst single sample: 2000 µg/L
3/3 SYR4 2014–2018
Copper
2.0735 µg/L 0.2%
of the EPA limit 1300 µg/L
worst single sample: 2.1 µg/L
2/3 SYR4 2014–2018
Combined Uranium
9.9305 µg/L 33%
of the EPA limit 30 µg/L
worst single sample: 10 µg/L
2/2 SYR4 2012–2018
Bromoform
0.8400 µg/L
No EPA limit set
1/6 SYR4 2013–2019
Combined Radium (-226 And -228)
0.6900 pCi/L 14%
of the EPA limit 5 pCi/L
1/1 SYR4 2015
Gross Alpha, Excl. Radon And U
5.2 pCi/L 35%
of the EPA limit 15 pCi/L
1/1 SYR4 2012
36 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-DichloropropaneAntimony, TotalBenzeneBeryllium, TotalBromodichloromethaneChlorobenzeneCyanideCarbon TetrachlorideChloroformDichloromethaneDibromoacetic AcidDibromochloromethaneDichloroacetic AcidEthylbenzeneMonobromoacetic AcidMonochloroacetic AcidNitriteStyreneTTHMTetrachloroethyleneThallium, TotalTolueneTotal Haloacetic Acids (HAA5)Trichloroacetic AcidTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
ALVAREZ-RUIZ, SAUL
Phone
702-296-4594
Email
[email protected]

Frequently asked questions about Luna Vista

Is Luna Vista tap water safe to drink?

EPA monitoring detected 10 contaminants in Luna Vista's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Luna Vista's water?

EPA monitoring detected Nitrate, Arsenic, Lead, Fluoride, Nitrate-Nitrite, and others. The full list with the level and data source for each is above.

How many people does Luna Vista serve?

Luna Vista reports serving 66 people in Nevada, per its EPA record.

Has Luna Vista had any water quality violations?

The EPA has 175 violations on file for Luna Vista, of which 20 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.