← Nevada

Tap water quality report

Equestrian Estates Co Op Water Assoc

EPA monitoring tested this supplier for 75 contaminants and detected 10. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

75
contaminants tested
10
detected
108
people served
104
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Clark

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

104
health-based violations
148
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2025-01-01 → 2025-03-31
MCL Health-based Resolved 2025-01-01 → 2025-03-31
MCL Health-based Resolved 2025-01-01 → 2025-03-31
MCL Health-based Resolved 2025-01-01 → 2025-03-31
MCL Health-based Resolved 2025-01-01 → 2025-03-31
MCL Health-based Resolved 2024-01-01 → 2024-03-31
MCL Health-based Resolved 2024-01-01 → 2024-03-31
MCL Health-based Resolved 2024-01-01 → 2024-03-31
MCL Health-based Resolved 2024-01-01 → 2024-03-31
MCL Health-based Resolved 2024-01-01 → 2024-03-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Arsenic
33.9 µg/L 339%
of the EPA limit, at the 95th percentile of samples — 10 µg/L
worst single sample: 38 µg/L
32/148 SYR4 2012–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
13/13 LCR 2025
Copper
225 µg/L 17%
of the EPA limit 1300 µg/L
worst single sample: 310 µg/L
11/14 SYR4 2012–2019
Nitrate
1800 µg/L 18%
of the EPA limit 10000 µg/L
10/18 SYR4 2012–2019
Lead
2.55 µg/L 17%
of the EPA limit 15 µg/L
worst single sample: 2.7 µg/L
4/12 SYR4 2012–2019
Nitrate-Nitrite
1695 µg/L 17%
of the EPA limit 10000 µg/L
worst single sample: 1800 µg/L
3/5 SYR4 2012–2019
Combined Uranium
8.608 µg/L 29%
of the EPA limit 30 µg/L
worst single sample: 8.94 µg/L
2/2 SYR4 2012–2018
Di(2-ethylhexyl) Phthalate
0.8425 µg/L 14%
of the EPA limit 6 µg/L
worst single sample: 0.8500 µg/L
2/9 SYR4 2013–2019
Fluoride
793 µg/L 20%
of the EPA limit 4000 µg/L
worst single sample: 800 µg/L
2/4 SYR4 2012–2019
Gross Alpha, Excl. Radon And U
1.76 pCi/L 12%
of the EPA limit 15 pCi/L
worst single sample: 1.8 pCi/L
2/2 SYR4 2012–2018
65 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalAtrazineBhc-GammaBariumBenzeneBenzo(A)PyreneBeryllium, TotalBromodichloromethaneBromoformChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChloroformChromiumCombined Radium (-226 And -228)DichloromethaneDalaponDi(2-ethylhexyl) AdipateDibromochloromethaneDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNitriteOxamylPentachlorophenolPicloramSeleniumSimazineStyreneTTHMTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
MILLER, KATIE
Phone
702-933-7764
Email
[email protected]

Frequently asked questions about Equestrian Estates Co Op Water Assoc

Is Equestrian Estates Co Op Water Assoc tap water safe to drink?

EPA monitoring detected 10 contaminants in Equestrian Estates Co Op Water Assoc's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Equestrian Estates Co Op Water Assoc's water?

EPA monitoring detected Arsenic, Lead, Copper, Nitrate, Lead, and others. The full list with the level and data source for each is above.

How many people does Equestrian Estates Co Op Water Assoc serve?

Equestrian Estates Co Op Water Assoc reports serving 108 people in Nevada, per its EPA record.

Has Equestrian Estates Co Op Water Assoc had any water quality violations?

The EPA has 148 violations on file for Equestrian Estates Co Op Water Assoc, of which 104 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.