Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Unaddressed | 2020-03-05 |
| TT | Health-based | Unaddressed | 2020-03-05 |
| MCL | Health-based | Resolved | 2006-07-01 → 2006-09-30 |
| MCL | Health-based | Resolved | 2006-07-01 → 2006-09-30 |
| MCL | Health-based | Resolved | 2006-07-01 → 2006-09-30 |
| MCL | Health-based | Resolved | 2006-07-01 → 2006-09-30 |
| MCL | Health-based | Resolved | 2006-06-01 → 2006-06-30 |
| MCL | Health-based | Resolved | 2006-06-01 → 2006-06-30 |
| MCL | Health-based | Resolved | 2006-06-01 → 2006-06-30 |
| MCL | Health-based | Resolved | 2006-05-01 → 2006-05-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 3095 µg/L 31% of the EPA limit 10000 µg/L
worst single sample: 3340 µg/L | 80/80 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 3100 µg/L 31% of the EPA limit 10000 µg/L
worst single sample: 3340 µg/L | 39/39 | SYR4 | 2012–2019 |
| Combined Uranium | 34.2 µg/L 114% of the EPA limit, at the 95th percentile of samples — 30 µg/L
worst single sample: 34.7 µg/L | 21/21 | SYR4 | 2012–2019 |
| Bromoform | 5.185 µg/L No EPA limit set
worst single sample: 6.8 µg/L | 18/31 | SYR4 | 2012–2019 |
| Dibromochloromethane | 6.305 µg/L No EPA limit set
worst single sample: 12 µg/L | 18/31 | SYR4 | 2012–2019 |
| TTHM | 20.15 µg/L 25% of the EPA limit 80 µg/L
worst single sample: 55 µg/L | 18/24 | SYR4 | 2012–2019 |
| Bromodichloromethane | 4.75 µg/L No EPA limit set
worst single sample: 13 µg/L | 16/31 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 1.97 µg/L No EPA limit set
worst single sample: 2.1 µg/L | 14/15 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 2.805 µg/L 4.7% of the EPA limit 60 µg/L
worst single sample: 3 µg/L | 14/15 | SYR4 | 2012–2019 |
| Arsenic | 3.45 µg/L 35% of the EPA limit 10 µg/L
worst single sample: 4 µg/L | 12/12 | SYR4 | 2012–2019 |
| Fluoride | 490 µg/L 12% of the EPA limit 4000 µg/L
worst single sample: 600 µg/L | 12/13 | SYR4 | 2012–2019 |
| Chloroform | 15.05 µg/L No EPA limit set
worst single sample: 23 µg/L | 11/31 | SYR4 | 2012–2019 |
| Combined Radium (-226 And -228) | 2.75 pCi/L 55% of the EPA limit 5 pCi/L
worst single sample: 2.9 pCi/L | 11/11 | SYR4 | 2012–2019 |
| Lead | 0.0020 mg/L 13% of the EPA limit 0.0150 mg/L | 11/11 | LCR | 2017 |
| Gross Alpha, Excl. Radon And U | 13.6 pCi/L 91% of the EPA limit 15 pCi/L
worst single sample: 14 pCi/L | 9/10 | SYR4 | 2012–2019 |
| Barium | 213 µg/L 11% of the EPA limit 2000 µg/L
worst single sample: 220 µg/L | 8/8 | SYR4 | 2012–2019 |
| Copper | 22.6 µg/L 1.7% of the EPA limit 1300 µg/L
worst single sample: 24 µg/L | 5/12 | SYR4 | 2012–2019 |
| Xylenes, Total | 14.65 µg/L 0.1% of the EPA limit 10000 µg/L
worst single sample: 16 µg/L | 3/21 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 2.05 µg/L No EPA limit set
worst single sample: 2.1 µg/L | 2/15 | SYR4 | 2012–2019 |
| Ethylbenzene | 1.634 µg/L 0.2% of the EPA limit 700 µg/L
worst single sample: 1.7 µg/L | 2/21 | SYR4 | 2012–2019 |
| Selenium | 1.95 µg/L 3.9% of the EPA limit 50 µg/L
worst single sample: 2 µg/L | 2/8 | SYR4 | 2012–2019 |
| Tetrachloroethylene | 0.3165 µg/L 6.3% of the EPA limit 5 µg/L
worst single sample: 0.3200 µg/L | 2/19 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 1.1 µg/L No EPA limit set | 1/15 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 1.8 µg/L No EPA limit set | 1/15 | SYR4 | 2012–2019 |
| Nitrite | 10 µg/L 1% of the EPA limit 1000 µg/L | 1/39 | SYR4 | 2012–2019 |
56 contaminants tested, none detected
Utility contact
Frequently asked questions about Jackpot Water
Is Jackpot Water tap water safe to drink?
EPA monitoring detected 25 contaminants in Jackpot Water's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Jackpot Water's water?
EPA monitoring detected Nitrate, Nitrate-Nitrite, Combined Uranium, Bromoform, Dibromochloromethane, and others. The full list with the level and data source for each is above.
How many people does Jackpot Water serve?
Jackpot Water reports serving 1,240 people in Nevada, per its EPA record.
Has Jackpot Water had any water quality violations?
The EPA has 161 violations on file for Jackpot Water, of which 19 are health-based (a contaminant limit or required treatment was breached) and 2 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.