← New Jersey

Tap water quality report

Alpha Municipal Water Works

EPA monitoring tested this supplier for 51 contaminants and detected 29. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

51
contaminants tested
29
detected
2,530
people served
12
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Warren

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

12
health-based violations
458
violations on file
3
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2011-10-01 → 2011-10-31
MCL Health-based Resolved 2011-10-01 → 2011-10-31
MCL Health-based Resolved 2011-10-01 → 2011-10-31
MCL Health-based Resolved 2011-10-01 → 2011-10-31
MCL Health-based Resolved 2011-08-01 → 2011-08-31
MCL Health-based Resolved 2011-08-01 → 2011-08-31
MCL Health-based Resolved 2011-08-01 → 2011-08-31
TT Health-based Resolved 2007-01-01
TT Health-based Resolved 2007-01-01
TT Health-based Resolved 2006-01-01

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
187.45 µg/L 14%
of the EPA limit 1300 µg/L
worst single sample: 342 µg/L
68/69 SYR4 2012–2019
Lead
4.28 µg/L 29%
of the EPA limit 15 µg/L
worst single sample: 16.3 µg/L
54/62 SYR4 2012–2019
Chloroform
2.965 µg/L
No EPA limit set
worst single sample: 32.3 µg/L
44/67 SYR4 2012–2019
Nitrate
5702.5 µg/L 57%
of the EPA limit 10000 µg/L
worst single sample: 5800 µg/L
36/36 SYR4 2012–2018
Trichloroethylene
0.5225 µg/L 10%
of the EPA limit 5 µg/L
worst single sample: 0.6600 µg/L
36/49 SYR4 2012–2019
Lead
0.0120 mg/L 80%
of the EPA limit 0.0150 mg/L
32/32 LCR 2025
Dibromochloromethane
8.1 µg/L
No EPA limit set
worst single sample: 10.2 µg/L
21/67 SYR4 2012–2019
Bromodichloromethane
7.221 µg/L
No EPA limit set
worst single sample: 13.8 µg/L
18/67 SYR4 2012–2019
TTHM
34.1 µg/L 43%
of the EPA limit 80 µg/L
worst single sample: 61.4 µg/L
15/18 SYR4 2012–2019
Bromoform
6.4 µg/L
No EPA limit set
worst single sample: 7.9 µg/L
13/67 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
15.485 µg/L 26%
of the EPA limit 60 µg/L
worst single sample: 17.9 µg/L
8/18 SYR4 2012–2019
Dibromoacetic Acid
5.74 µg/L
No EPA limit set
worst single sample: 6.37 µg/L
7/18 SYR4 2012–2019
Dichloroacetic Acid
10.125 µg/L
No EPA limit set
worst single sample: 12.5 µg/L
6/18 SYR4 2012–2019
Barium
39.44 µg/L 2%
of the EPA limit 2000 µg/L
worst single sample: 39.8 µg/L
5/7 SYR4 2012–2018
Combined Radium (-226 And -228)
1.5 pCi/L 30%
of the EPA limit 5 pCi/L
5/5 SYR4 2012–2018
Selenium
3.62 µg/L 7.2%
of the EPA limit 50 µg/L
worst single sample: 3.8 µg/L
5/7 SYR4 2012–2018
Arsenic
0.5755 µg/L 5.8%
of the EPA limit 10 µg/L
worst single sample: 0.5800 µg/L
4/7 SYR4 2012–2018
Nitrate-Nitrite
5665 µg/L 57%
of the EPA limit 10000 µg/L
worst single sample: 5680 µg/L
4/4 SYR4 2018–2019
Chromium
2.84 µg/L 2.8%
of the EPA limit 100 µg/L
worst single sample: 2.9 µg/L
3/7 SYR4 2012–2018
Trichloroacetic Acid
6.251 µg/L
No EPA limit set
worst single sample: 6.76 µg/L
3/18 SYR4 2012–2019
Antimony, Total
0.0400 µg/L 0.7%
of the EPA limit 6 µg/L
1/7 SYR4 2012–2018
Cyanide
1.1 µg/L 0.6%
of the EPA limit 200 µg/L
1/7 SYR4 2012–2018
Ethylbenzene
0.0700 µg/L 0%
of the EPA limit 700 µg/L
1/49 SYR4 2012–2019
Mercury
0.4000 µg/L 20%
of the EPA limit 2 µg/L
1/7 SYR4 2012–2018
Monobromoacetic Acid
0.3600 µg/L
No EPA limit set
1/18 SYR4 2012–2019
Monochloroacetic Acid
3.84 µg/L
No EPA limit set
1/18 SYR4 2012–2019
Tetrachloroethylene
0.0800 µg/L 1.6%
of the EPA limit 5 µg/L
1/49 SYR4 2012–2019
Toluene
1.52 µg/L 0.2%
of the EPA limit 1000 µg/L
1/49 SYR4 2012–2019
Xylenes, Total
0.4600 µg/L 0%
of the EPA limit 10000 µg/L
1/49 SYR4 2012–2019
22 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-DichloropropaneBenzeneBeryllium, TotalChlorobenzeneCadmiumCarbon TetrachlorideDichloromethaneEthylene DibromideFluorideStyreneThallium, TotalVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
DUNWELL, CRAIG S
Phone
908-454-0088

Frequently asked questions about Alpha Municipal Water Works

Is Alpha Municipal Water Works tap water safe to drink?

EPA monitoring detected 29 contaminants in Alpha Municipal Water Works's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Alpha Municipal Water Works's water?

EPA monitoring detected Copper, Lead, Chloroform, Nitrate, Trichloroethylene, and others. The full list with the level and data source for each is above.

How many people does Alpha Municipal Water Works serve?

Alpha Municipal Water Works reports serving 2,530 people in New Jersey, per its EPA record.

Has Alpha Municipal Water Works had any water quality violations?

The EPA has 458 violations on file for Alpha Municipal Water Works, of which 12 are health-based (a contaminant limit or required treatment was breached) and 3 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.