← New Jersey

Tap water quality report

Veolia Water New Jersey David Curtis

EPA monitoring tested this supplier for 55 contaminants and detected 21. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

55
contaminants tested
21
detected
53
people served
4
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Sussex

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

4
health-based violations
123
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2008-12-01 → 2008-12-31
MCL Health-based Resolved 2008-12-01 → 2008-12-31
MCL Health-based Resolved 2008-12-01 → 2008-12-31
MCL Health-based Resolved 2008-12-01 → 2008-12-31
MR Monitoring Resolved 2011-01-01 → 2013-12-31
MR Monitoring Resolved 2011-01-01 → 2013-12-31
MR Monitoring Resolved 2011-01-01 → 2013-12-31
MR Monitoring Resolved 2011-01-01 → 2013-12-31
MR Monitoring Resolved 2011-01-01 → 2013-12-31
MR Monitoring Resolved 2011-01-01 → 2013-12-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
251.2 µg/L 19%
of the EPA limit 1300 µg/L
worst single sample: 512 µg/L
54/54 SYR4 2012–2019
Lead
0.0078 mg/L 52%
of the EPA limit 0.0150 mg/L
25/25 LCR 2026
Lead
21.985 µg/L 147%
of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 27 µg/L
22/52 SYR4 2012–2019
Nitrate-Nitrite
1992 µg/L 20%
of the EPA limit 10000 µg/L
worst single sample: 2020 µg/L
8/8 SYR4 2012–2019
TTHM
25.495 µg/L 32%
of the EPA limit 80 µg/L
worst single sample: 32.6 µg/L
8/8 SYR4 2012–2019
Chloroform
21.85 µg/L
No EPA limit set
worst single sample: 25.6 µg/L
6/10 SYR4 2012–2019
Combined Uranium
28.7 µg/L 96%
of the EPA limit 30 µg/L
worst single sample: 29.3 µg/L
6/6 SYR4 2012–2018
Dibromochloromethane
1.58 µg/L
No EPA limit set
worst single sample: 1.84 µg/L
6/10 SYR4 2012–2019
Nitrate
2020 µg/L 20%
of the EPA limit 10000 µg/L
6/6 SYR4 2012–2019
Bromodichloromethane
3.89 µg/L
No EPA limit set
worst single sample: 4.55 µg/L
5/10 SYR4 2012–2019
Gross Alpha, Excl. Radon And U
3.6065 pCi/L 24%
of the EPA limit 15 pCi/L
worst single sample: 3.89 pCi/L
4/6 SYR4 2012–2018
Arsenic
2.05 µg/L 21%
of the EPA limit 10 µg/L
worst single sample: 2.1 µg/L
3/3 SYR4 2012–2018
Barium
6.251 µg/L 0.3%
of the EPA limit 2000 µg/L
worst single sample: 6.29 µg/L
3/3 SYR4 2012–2018
Chromium
12.89 µg/L 13%
of the EPA limit 100 µg/L
worst single sample: 13.1 µg/L
3/3 SYR4 2012–2018
Fluoride
543 µg/L 14%
of the EPA limit 4000 µg/L
worst single sample: 550 µg/L
3/3 SYR4 2012–2018
Total Haloacetic Acids (HAA5)
5.616 µg/L 9.4%
of the EPA limit 60 µg/L
worst single sample: 6 µg/L
3/8 SYR4 2012–2019
Bromoform
0.7695 µg/L
No EPA limit set
worst single sample: 0.7800 µg/L
2/10 SYR4 2012–2019
Combined Radium (-226 And -228)
2.82 pCi/L 56%
of the EPA limit 5 pCi/L
worst single sample: 2.9 pCi/L
2/6 SYR4 2012–2018
Dichloroacetic Acid
3.855 µg/L
No EPA limit set
worst single sample: 4 µg/L
2/8 SYR4 2012–2019
Monochloroacetic Acid
2.152 µg/L
No EPA limit set
worst single sample: 2.16 µg/L
2/8 SYR4 2012–2019
Mercury
0.4060 µg/L 20%
of the EPA limit 2 µg/L
1/3 SYR4 2012–2018
34 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-DichloropropaneAntimony, TotalAsbestosBenzeneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbon TetrachlorideDichloromethaneDibromoacetic AcidEthylene DibromideEthylbenzeneMonobromoacetic AcidNitriteSeleniumStyreneTetrachloroethyleneThallium, TotalTolueneTrichloroacetic AcidTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
DECARLO, LYNN MARIE
Phone
201-599-6020

Frequently asked questions about Veolia Water New Jersey David Curtis

Is Veolia Water New Jersey David Curtis tap water safe to drink?

EPA monitoring detected 21 contaminants in Veolia Water New Jersey David Curtis's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Veolia Water New Jersey David Curtis's water?

EPA monitoring detected Copper, Lead, Lead, Nitrate-Nitrite, TTHM, and others. The full list with the level and data source for each is above.

How many people does Veolia Water New Jersey David Curtis serve?

Veolia Water New Jersey David Curtis reports serving 53 people in New Jersey, per its EPA record.

Has Veolia Water New Jersey David Curtis had any water quality violations?

The EPA has 123 violations on file for Veolia Water New Jersey David Curtis, of which 4 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.