← New Jersey

Tap water quality report

Aqua Nj - Vernon

EPA monitoring tested this supplier for 72 contaminants and detected 23. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

72
contaminants tested
23
detected
515
people served
8
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Sussex

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

8
health-based violations
94
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2007-01-01 → 2007-03-31
MCL Health-based Resolved 2007-01-01 → 2007-03-31
MCL Health-based Resolved 2007-01-01 → 2007-03-31
MCL Health-based Resolved 2007-01-01 → 2007-03-31
MCL Health-based Resolved 2006-01-01 → 2006-01-31
MCL Health-based Resolved 2006-01-01 → 2006-01-31
MCL Health-based Resolved 2006-01-01 → 2006-01-31
MCL Health-based Resolved 2006-01-01 → 2006-01-31
RPT Monitoring Resolved 2021-05-11
RPT Monitoring Resolved 2021-05-11

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate
3500 µg/L 35%
of the EPA limit 10000 µg/L
worst single sample: 3800 µg/L
42/44 SYR4 2012–2019
Copper
365 µg/L 28%
of the EPA limit 1300 µg/L
worst single sample: 460 µg/L
27/50 SYR4 2012–2018
Dibromochloromethane
3.1 µg/L
No EPA limit set
worst single sample: 3.2 µg/L
21/25 SYR4 2012–2019
Bromodichloromethane
3.915 µg/L
No EPA limit set
worst single sample: 4.2 µg/L
20/25 SYR4 2012–2019
Lead
15.25 µg/L 102%
of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 20 µg/L
20/31 SYR4 2012–2018
Fluoride
213 µg/L 5.3%
of the EPA limit 4000 µg/L
worst single sample: 240 µg/L
19/19 SYR4 2012–2018
Nitrate-Nitrite
3545 µg/L 35%
of the EPA limit 10000 µg/L
worst single sample: 3800 µg/L
18/19 SYR4 2012–2019
Chloroform
5.02 µg/L
No EPA limit set
worst single sample: 5.1 µg/L
17/25 SYR4 2012–2019
Chromium
9 µg/L 9%
of the EPA limit 100 µg/L
worst single sample: 13 µg/L
17/19 SYR4 2012–2018
Barium
26.7 µg/L 1.3%
of the EPA limit 2000 µg/L
worst single sample: 28 µg/L
14/19 SYR4 2012–2018
Lead
0.0041 mg/L 27%
of the EPA limit 0.0150 mg/L
14/14 LCR 2024
TTHM
11.175 µg/L 14%
of the EPA limit 80 µg/L
worst single sample: 11.5 µg/L
14/17 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
5.82 µg/L 9.7%
of the EPA limit 60 µg/L
worst single sample: 6.1 µg/L
9/17 SYR4 2012–2019
Combined Uranium
15.52 µg/L 52%
of the EPA limit 30 µg/L
worst single sample: 15.7 µg/L
5/5 SYR4 2012–2018
Dichloroacetic Acid
2.6 µg/L
No EPA limit set
5/17 SYR4 2012–2019
Gross Alpha, Excl. Radon And U
9.8 pCi/L 65%
of the EPA limit 15 pCi/L
worst single sample: 11 pCi/L
5/5 SYR4 2012–2018
Trichloroacetic Acid
1.2 µg/L
No EPA limit set
4/17 SYR4 2012–2019
Bromoform
0.6900 µg/L
No EPA limit set
worst single sample: 0.7000 µg/L
3/25 SYR4 2012–2019
Dibromoacetic Acid
1.3 µg/L
No EPA limit set
3/17 SYR4 2012–2019
Monochloroacetic Acid
5.75 µg/L
No EPA limit set
worst single sample: 6.1 µg/L
3/17 SYR4 2012–2019
Arsenic
1.89 µg/L 19%
of the EPA limit 10 µg/L
worst single sample: 1.9 µg/L
2/19 SYR4 2012–2018
Combined Radium (-226 And -228)
0.6500 pCi/L 13%
of the EPA limit 5 pCi/L
1/5 SYR4 2012–2018
Selenium
1 µg/L 2%
of the EPA limit 50 µg/L
1/19 SYR4 2012–2018
49 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalAsbestosAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbon TetrachlorideDichloromethaneDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebEthylene DibromideEndrinEthylbenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidNitritePentachlorophenolPicloramSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
VANIM, ALYSSA
Phone
609-618-3850
Email
[email protected]

Frequently asked questions about Aqua Nj - Vernon

Is Aqua Nj - Vernon tap water safe to drink?

EPA monitoring detected 23 contaminants in Aqua Nj - Vernon's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Aqua Nj - Vernon's water?

EPA monitoring detected Nitrate, Copper, Dibromochloromethane, Bromodichloromethane, Lead, and others. The full list with the level and data source for each is above.

How many people does Aqua Nj - Vernon serve?

Aqua Nj - Vernon reports serving 515 people in New Jersey, per its EPA record.

Has Aqua Nj - Vernon had any water quality violations?

The EPA has 94 violations on file for Aqua Nj - Vernon, of which 8 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.