Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2012-08-01 → 2012-08-31 |
| MCL | Health-based | Resolved | 2012-08-01 → 2012-08-31 |
| MCL | Health-based | Resolved | 2012-08-01 → 2012-08-31 |
| MCL | Health-based | Resolved | 2012-06-01 → 2012-06-30 |
| MCL | Health-based | Resolved | 2012-06-01 → 2012-06-30 |
| MCL | Health-based | Resolved | 2012-06-01 → 2012-06-30 |
| MCL | Health-based | Resolved | 2012-06-01 → 2012-06-30 |
| MCL | Health-based | Resolved | 2012-05-01 → 2012-05-31 |
| MCL | Health-based | Resolved | 2012-05-01 → 2012-05-31 |
| MCL | Health-based | Resolved | 2012-05-01 → 2012-05-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 387.8 µg/L 30% of the EPA limit 1300 µg/L
worst single sample: 852 µg/L | 55/56 | SYR4 | 2012–2019 |
| Lead | 14.01 µg/L 93% of the EPA limit 15 µg/L
worst single sample: 44 µg/L | 43/52 | SYR4 | 2012–2019 |
| Lead | 0.0126 mg/L 84% of the EPA limit 0.0150 mg/L | 31/31 | LCR | 2026 |
| Chloroform | 3.919 µg/L No EPA limit set
worst single sample: 4.6 µg/L | 7/12 | SYR4 | 2012–2019 |
| Fluoride | 331.8 µg/L 8.3% of the EPA limit 4000 µg/L
worst single sample: 333 µg/L | 7/7 | SYR4 | 2012–2018 |
| Bromodichloromethane | 4.305 µg/L No EPA limit set
worst single sample: 5.1 µg/L | 6/12 | SYR4 | 2012–2019 |
| Dibromochloromethane | 5.4325 µg/L No EPA limit set
worst single sample: 6.6 µg/L | 6/10 | SYR4 | 2012–2019 |
| TTHM | 16.17 µg/L 20% of the EPA limit 80 µg/L
worst single sample: 19.5 µg/L | 6/7 | SYR4 | 2013–2019 |
| Barium | 45.55 µg/L 2.3% of the EPA limit 2000 µg/L
worst single sample: 45.7 µg/L | 4/4 | SYR4 | 2012–2018 |
| Bromoform | 2.901 µg/L No EPA limit set
worst single sample: 3.2 µg/L | 3/12 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 1.73 µg/L No EPA limit set
worst single sample: 1.8 µg/L | 3/7 | SYR4 | 2013–2019 |
| Selenium | 1.564 µg/L 3.1% of the EPA limit 50 µg/L
worst single sample: 1.7 µg/L | 3/4 | SYR4 | 2012–2018 |
| Total Haloacetic Acids (HAA5) | 5.33 µg/L 8.9% of the EPA limit 60 µg/L
worst single sample: 5.8 µg/L | 3/7 | SYR4 | 2013–2019 |
| Arsenic | 0.6045 µg/L 6% of the EPA limit 10 µg/L
worst single sample: 0.6200 µg/L | 2/4 | SYR4 | 2012–2018 |
| Combined Radium (-226 And -228) | 4.008 pCi/L 80% of the EPA limit 5 pCi/L
worst single sample: 4.14 pCi/L | 2/2 | SYR4 | 2012–2015 |
| Chromium | 1 µg/L 1% of the EPA limit 100 µg/L | 1/4 | SYR4 | 2012–2018 |
| Dibromoacetic Acid | 2.5 µg/L No EPA limit set | 1/7 | SYR4 | 2013–2019 |
| Monochloroacetic Acid | 0.4100 µg/L No EPA limit set | 1/7 | SYR4 | 2013–2019 |
| Trichloroacetic Acid | 1.5 µg/L No EPA limit set | 1/7 | SYR4 | 2013–2019 |
31 contaminants tested, none detected
Utility contact
Frequently asked questions about Leisure Arms Complex
Is Leisure Arms Complex tap water safe to drink?
EPA monitoring detected 19 contaminants in Leisure Arms Complex's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Leisure Arms Complex's water?
EPA monitoring detected Copper, Lead, Lead, Chloroform, Fluoride, and others. The full list with the level and data source for each is above.
How many people does Leisure Arms Complex serve?
Leisure Arms Complex reports serving 60 people in New Jersey, per its EPA record.
Has Leisure Arms Complex had any water quality violations?
The EPA has 116 violations on file for Leisure Arms Complex, of which 17 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?