← New Jersey

Tap water quality report

Hawthorne Water Department

EPA monitoring tested this supplier for 100 contaminants and detected 27. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

100
contaminants tested
27
detected
19,458
people served
9
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Bergen, Passaic

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

9
health-based violations
624
violations on file
1
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 2022-01-10
TT Health-based Resolved 2022-01-10
TT Health-based Resolved 2022-01-10
TT Health-based Resolved 2022-01-10
TT Health-based Resolved 2006-04-19
TT Health-based Resolved 2006-04-19
TT Health-based Resolved 2006-04-19
TT Health-based Resolved 2004-01-01 → 2004-12-31
TT Health-based Resolved 2004-01-01 → 2004-12-31
MR Monitoring Resolved 2025-10-01 → 2025-12-31

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
Pfba 0.0093 µg/L 5/8 2025
Pfpea 0.0087 µg/L 2/8 2025

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Bromoform
12.14 µg/L
No EPA limit set
worst single sample: 17.9 µg/L
144/203 SYR4 2012–2019
Dibromochloromethane
11.27 µg/L
No EPA limit set
worst single sample: 14.4 µg/L
143/203 SYR4 2012–2019
TTHM
30.34 µg/L 38%
of the EPA limit 80 µg/L
worst single sample: 37 µg/L
127/128 SYR4 2012–2019
Bromodichloromethane
5.742 µg/L
No EPA limit set
worst single sample: 7.69 µg/L
118/203 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
7.1785 µg/L 12%
of the EPA limit 60 µg/L
worst single sample: 8.77 µg/L
112/128 SYR4 2012–2019
Dibromoacetic Acid
4.61 µg/L
No EPA limit set
worst single sample: 5.43 µg/L
111/128 SYR4 2012–2019
Nitrate
5550 µg/L 56%
of the EPA limit 10000 µg/L
worst single sample: 6450 µg/L
96/96 SYR4 2012–2019
Chloroform
3.77 µg/L
No EPA limit set
worst single sample: 12 µg/L
85/203 SYR4 2012–2019
Copper
131 µg/L 10%
of the EPA limit 1300 µg/L
worst single sample: 143 µg/L
62/105 SYR4 2012–2018
Dichloroacetic Acid
2.626 µg/L
No EPA limit set
worst single sample: 3.8 µg/L
30/128 SYR4 2012–2019
Lead
7.524 µg/L 50%
of the EPA limit 15 µg/L
worst single sample: 18.7 µg/L
29/97 SYR4 2012–2018
Monobromoacetic Acid
1.4275 µg/L
No EPA limit set
worst single sample: 1.45 µg/L
26/128 SYR4 2012–2019
Lead
0.0031 mg/L 20%
of the EPA limit 0.0150 mg/L
22/22 LCR 2024
Nitrate-Nitrite
3409 µg/L 34%
of the EPA limit 10000 µg/L
worst single sample: 3750 µg/L
12/12 SYR4 2012–2017
Barium
810.85 µg/L 41%
of the EPA limit 2000 µg/L
worst single sample: 814 µg/L
8/8 SYR4 2014–2017
Chromium
0.9625 µg/L 1%
of the EPA limit 100 µg/L
worst single sample: 0.9680 µg/L
4/8 SYR4 2014–2017
Mercury
0.0386 µg/L 1.9%
of the EPA limit 2 µg/L
worst single sample: 0.0400 µg/L
4/8 SYR4 2014–2017
Monochloroacetic Acid
2.79 µg/L
No EPA limit set
worst single sample: 3 µg/L
4/128 SYR4 2012–2019
Trichloroacetic Acid
1.2885 µg/L
No EPA limit set
worst single sample: 1.29 µg/L
4/128 SYR4 2012–2019
Arsenic
1.8945 µg/L 19%
of the EPA limit 10 µg/L
worst single sample: 1.93 µg/L
2/8 SYR4 2014–2017
Combined Uranium
1.5325 µg/L 5.1%
of the EPA limit 30 µg/L
worst single sample: 1.56 µg/L
2/2 SYR4 2017
Selenium
3.1375 µg/L 6.3%
of the EPA limit 50 µg/L
worst single sample: 3.2 µg/L
2/8 SYR4 2014–2017
Thallium, Total
0.6219 µg/L 31%
of the EPA limit 2 µg/L
worst single sample: 0.6240 µg/L
2/8 SYR4 2014–2017
Cyanide
5 µg/L 2.5%
of the EPA limit 200 µg/L
1/8 SYR4 2014–2017
Dichloromethane
3.81 µg/L 76%
of the EPA limit 5 µg/L
1/75 SYR4 2012–2019
73 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCadmiumCarbon TetrachlorideCombined Radium (-226 And -228)Di(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebEthylene DibromideEndrinEthylbenzeneFluorideHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMethoxychlorNetfosaaNfdhaNmefosaaNitritePFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpesPftaPftrdaPfunaPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneTolueneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
HAFFLER, WILLIAM
Phone
973-427-7707

Frequently asked questions about Hawthorne Water Department

Is Hawthorne Water Department tap water safe to drink?

EPA monitoring detected 27 contaminants in Hawthorne Water Department's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Hawthorne Water Department's water?

EPA monitoring detected Bromoform, Dibromochloromethane, TTHM, Bromodichloromethane, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.

How many people does Hawthorne Water Department serve?

Hawthorne Water Department reports serving 19,458 people in New Jersey, per its EPA record.

Has Hawthorne Water Department had any water quality violations?

The EPA has 624 violations on file for Hawthorne Water Department, of which 9 are health-based (a contaminant limit or required treatment was breached) and 1 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.