← New Jersey

Tap water quality report

Barnegat Twp Water Sewer

EPA monitoring tested this supplier for 82 contaminants and detected 20. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

82
contaminants tested
20
detected
20,000
people served
7
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Ocean

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

7
health-based violations
199
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2010-06-01 → 2010-06-30
MCL Health-based Resolved 2010-06-01 → 2010-06-30
MCL Health-based Resolved 2010-06-01 → 2010-06-30
MCL Health-based Resolved 2010-06-01 → 2010-06-30
MCL Health-based Resolved 2008-08-01 → 2008-08-31
MCL Health-based Resolved 2008-08-01 → 2008-08-31
MCL Health-based Resolved 2008-08-01 → 2008-08-31
MR Monitoring Archived 2023-08-01 → 2023-10-31
MR Monitoring Archived 2023-08-01 → 2023-10-31
MR Monitoring Archived 2023-08-01 → 2023-10-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Chloroform
2.319 µg/L
No EPA limit set
worst single sample: 7.06 µg/L
120/123 SYR4 2012–2019
TTHM
4.5015 µg/L 5.6%
of the EPA limit 80 µg/L
worst single sample: 15.1 µg/L
120/123 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
11.11 µg/L 19%
of the EPA limit 60 µg/L
worst single sample: 20 µg/L
104/123 SYR4 2012–2019
Bromodichloromethane
1.23 µg/L
No EPA limit set
worst single sample: 3.08 µg/L
86/123 SYR4 2012–2019
Dichloroacetic Acid
2.9455 µg/L
No EPA limit set
worst single sample: 5.08 µg/L
84/123 SYR4 2012–2019
Dibromochloromethane
1.45 µg/L
No EPA limit set
worst single sample: 3.41 µg/L
83/123 SYR4 2012–2019
Monochloroacetic Acid
10.7 µg/L
No EPA limit set
worst single sample: 14.3 µg/L
73/123 SYR4 2012–2019
Dibromoacetic Acid
2.3575 µg/L
No EPA limit set
worst single sample: 6.41 µg/L
40/123 SYR4 2012–2019
Trichloroacetic Acid
1.833 µg/L
No EPA limit set
worst single sample: 2.94 µg/L
38/123 SYR4 2012–2019
Nitrate
975 µg/L 9.8%
of the EPA limit 10000 µg/L
worst single sample: 1000 µg/L
26/62 SYR4 2012–2019
Bromoform
1.48 µg/L
No EPA limit set
worst single sample: 1.69 µg/L
25/123 SYR4 2012–2019
Monobromoacetic Acid
1.6 µg/L
No EPA limit set
worst single sample: 1.68 µg/L
21/123 SYR4 2012–2019
Combined Radium (-226 And -228)
5.1795 pCi/L 104%
of the EPA limit, at the 95th percentile of samples — 5 pCi/L
worst single sample: 5.74 pCi/L
20/20 SYR4 2012–2019
Lead
0.00070 mg/L 4.7%
of the EPA limit 0.0150 mg/L
16/16 LCR 2025
Barium
294.5 µg/L 15%
of the EPA limit 2000 µg/L
worst single sample: 300 µg/L
12/14 SYR4 2013–2019
Copper
63 µg/L 4.8%
of the EPA limit 1300 µg/L
worst single sample: 70 µg/L
8/104 SYR4 2013–2019
Lead
9.55 µg/L 64%
of the EPA limit 15 µg/L
worst single sample: 10 µg/L
4/90 SYR4 2013–2019
Gross Alpha, Excl. Radon And U
16.0453 pCi/L 107%
of the EPA limit, at the 95th percentile of samples — 15 pCi/L
worst single sample: 17.007 pCi/L
3/3 SYR4 2012–2018
Xylenes, Total
1.9185 µg/L 0%
of the EPA limit 10000 µg/L
worst single sample: 1.98 µg/L
2/27 SYR4 2013–2019
Nitrate-Nitrite
900 µg/L 9%
of the EPA limit 10000 µg/L
1/1 SYR4 2013
62 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalArsenicBenzeneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbon TetrachlorideChromiumCombined UraniumDichloromethaneEthylbenzeneFluorideHfpo-DaMercuryNetfosaaNfdhaNmefosaaNitritePfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaSeleniumStyreneTetrachloroethyleneThallium, TotalTolueneTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
BUDD JR, ROGER A
Phone
609-696-6185

Frequently asked questions about Barnegat Twp Water Sewer

Is Barnegat Twp Water Sewer tap water safe to drink?

EPA monitoring detected 20 contaminants in Barnegat Twp Water Sewer's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Barnegat Twp Water Sewer's water?

EPA monitoring detected Chloroform, TTHM, Total Haloacetic Acids (HAA5), Bromodichloromethane, Dichloroacetic Acid, and others. The full list with the level and data source for each is above.

How many people does Barnegat Twp Water Sewer serve?

Barnegat Twp Water Sewer reports serving 20,000 people in New Jersey, per its EPA record.

Has Barnegat Twp Water Sewer had any water quality violations?

The EPA has 199 violations on file for Barnegat Twp Water Sewer, of which 7 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.