← New Jersey

Tap water quality report

Seaside Heights Water De

EPA monitoring tested this supplier for 78 contaminants and detected 17. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

78
contaminants tested
17
detected
20,000
people served
0
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Ocean

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

0
health-based violations
27
violations on file
0
still open
ViolationTypeStatusPeriod
RPT Monitoring Resolved 2017-07-11
RPT Monitoring Resolved 2017-07-11
Other Monitoring Resolved 2016-07-01
Other Monitoring Resolved 2016-07-01
MR Monitoring Resolved 2012-07-01 → 2012-07-31
MR Monitoring Resolved 2012-07-01 → 2012-07-31
MR Monitoring Resolved 2012-07-01 → 2012-07-31
Other Monitoring Resolved 2011-10-01
Other Monitoring Resolved 2011-10-01
Other Monitoring Resolved 2011-07-01

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Bromodichloromethane
3.135 µg/L
No EPA limit set
worst single sample: 3.71 µg/L
26/26 SYR4 2012–2019
Dibromochloromethane
10.5875 µg/L
No EPA limit set
worst single sample: 12.65 µg/L
26/26 SYR4 2012–2019
TTHM
71.9 µg/L 90%
of the EPA limit 80 µg/L
worst single sample: 84.5 µg/L
26/26 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
17.86 µg/L 30%
of the EPA limit 60 µg/L
worst single sample: 26 µg/L
23/26 SYR4 2012–2019
Chloroform
3.498 µg/L
No EPA limit set
worst single sample: 4.58 µg/L
22/26 SYR4 2012–2019
Dichloroacetic Acid
3.8885 µg/L
No EPA limit set
worst single sample: 4.81 µg/L
20/26 SYR4 2012–2019
Dibromoacetic Acid
11.5 µg/L
No EPA limit set
worst single sample: 12.3 µg/L
17/26 SYR4 2012–2019
Lead
0.0016 mg/L 11%
of the EPA limit 0.0150 mg/L
16/16 LCR 2025
Monobromoacetic Acid
1.7425 µg/L
No EPA limit set
worst single sample: 2.05 µg/L
16/26 SYR4 2012–2019
Bromoform
65.9475 µg/L
No EPA limit set
worst single sample: 69.1 µg/L
14/26 SYR4 2012–2019
Trichloroacetic Acid
2.136 µg/L
No EPA limit set
worst single sample: 2.94 µg/L
13/26 SYR4 2012–2019
Copper
210 µg/L 16%
of the EPA limit 1300 µg/L
worst single sample: 300 µg/L
10/33 SYR4 2012–2019
Monochloroacetic Acid
10.84 µg/L
No EPA limit set
worst single sample: 11 µg/L
9/26 SYR4 2012–2019
Nitrate
700 µg/L 7%
of the EPA limit 10000 µg/L
6/16 SYR4 2012–2019
Lead
2 µg/L 13%
of the EPA limit 15 µg/L
3/30 SYR4 2013–2019
Barium
195 µg/L 9.8%
of the EPA limit 2000 µg/L
worst single sample: 200 µg/L
2/3 SYR4 2012–2018
Combined Radium (-226 And -228)
1.5 pCi/L 30%
of the EPA limit 5 pCi/L
1/1 SYR4 2017
61 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalArsenicBenzeneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbon TetrachlorideChromiumDichloromethaneEthylbenzeneFluorideHfpo-DaMercuryNetfosaaNfdhaNmefosaaPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaSeleniumStyreneTetrachloroethyleneThallium, TotalTolueneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
VAS, CHRISTOPHER
Phone
732-793-9100

Frequently asked questions about Seaside Heights Water De

Is Seaside Heights Water De tap water safe to drink?

EPA monitoring detected 17 contaminants in Seaside Heights Water De's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Seaside Heights Water De's water?

EPA monitoring detected Bromodichloromethane, Dibromochloromethane, TTHM, Total Haloacetic Acids (HAA5), Chloroform, and others. The full list with the level and data source for each is above.

How many people does Seaside Heights Water De serve?

Seaside Heights Water De reports serving 20,000 people in New Jersey, per its EPA record.

Has Seaside Heights Water De had any water quality violations?

The EPA has 27 violations on file for Seaside Heights Water De, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.